Cut Sheet

NH DIN Dual Indication Fuse Links NH
Class gG/gL, 500Vac, 10 to 160 Amps, Size 0
Size 0 Technical Data
Size 0 Time-Current Characteristics
23-04-09 SB-SB09366 Form No.NH500V
Page 4 of 9 Data Sheet 2142
Part
Number
Amp
Rating
I
2
t (Amps
2
Seconds)
Watts
Loss
Net Weight
per Fuse
Minimum
Pre-arcing
20 x I
n
@ 500V
ac
*I
1
120kA
@ 500V
ac
10NHG0B 10 58 290 240 2.0
0.26kg
16NHG0B 16 240 1200 1000 3.0
20NHG0B 20 490 2500 2000 3.6
25NHG0B 25 1200 5600 4500 4.0
32NHG0B 32 1800 9000 7200 5.1
35NHG0B 35 2400 11800 9400 5.2
40NHG0B 40 3300 16500 13200 5.6
50NHG0B 50 5600 22300 16700 7.0
63NHG0B 63 6600 26100 19600 7.0
80NHG0B 80 9800 38900 29200 7.9
100NHG0B 100 20600 82300 61700 9.2
125NHG0B 125 25000 125000 72500 13.1
160NHG0B 160 62000 310000 179800 14.1
* I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
Dimensions - mm
TIME (Seconds)
6
842682648 246
10 100 1000
2
6
4
0.1
0.01
1
6
4
2
6
2
4
10
100
6
4
2
6
4
2
6
4
2
1000
10 000
32
35
40
50
63
80
100
125
160
16
10
20
25
250
224
200
CURRENT (Amps)