Cut Sheet
Pipe Hangers
E Adjustment F Design Load Approx. Wt./100
Part No. in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
B3100-
1
/2 2
1
/2" (63.5)
7
/16" (11.1) 730 (3.25) 25 (11.3)
B3100-
3
/4 2
1
/2" (63.5)
1
/2" (12.7) 730 (3.25) 29 (13.1)
B3100-1 2
1
/2" (63.5)
5
/8" (15.9) 730 (3.25) 35 (15.9)
B3100-1
1
/4 2
1
/2" (63.5)
7
/8" (22.2) 730 (3.25) 40 (18.1)
B3100-1
1
/2 2
1
/2" (63.5) 1
3
/16" (30.2) 730 (3.25) 42 (19.0)
B3100-2 * 2
1
/2" (63.5) 1
5
/8" (41.3) 730 (3.25) 52 (23.6)
B3100-2
1
/2 * 2
1
/2" (63.5) 2" (50.8) 1350 (6.00) 90 (40.8)
B3100-3 * 2
1
/2" (63.5) 2" (50.8) 1350 (6.00) 110 (49.9)
B3100-3
1
/2 2
1
/2" (63.5) 2" (50.8) 1350 (6.00) 142 (64.4)
B3100-4 * 2
1
/2" (63.5) 2" (50.8) 1430
(6.36) 132 (59.9)
B3100-5 * 2
1
/2" (63.5) 2" (50.8) 1430
(6.36) 215 (97.5)
B3100-6 * 3" (76.2) 2" (50.8) 1940
(8.63) 320 (145.1)
B3100-8 3
1
/2" (88.9) 2
5
/16" (58.7) 2000
(8.89) 485 (220.0)
B3100-10 3
1
/2" (88.9) 2
5
/16" (58.7) 3600
(16.01) 846 (383.7)
B3100-12 3
1
/2" (88.9) 2
5
/8" (66.7) 3800
(16.90) 1083 (491.2)
B3100-14 4" (101.6) 2
7
/8" (73.0) 4200
(18.68) 1432 (649.5)
B3100-16 4" (101.6) 2
11
/16" (68.3) 4600
(20.46) 2200 (997.9)
B3100-18 4
1
/2" (114.3) 3
15
/16" (100.0) 4800
(21.35) 2500 (1134.0)
B3100-20 5" (127.0) 5
3
/8" (136.5) 4800
(21.35) 4400 (1995.8)
B3100-24 5" (127.0) 5
3
/8" (136.5) 4800
(21.35) 5000 (2268.0)
B3100-30 5" (127.0) 6
1
/4" (158.7) 6000
(26.69) 6600 (2993.7)
B3100-36 5" (127.0 5
7
/16" (138.1) 6000
(26.69) 8474 (3843.8)
Size Range:
1
/2” (15mm) to 36” (900mm)
Material: Steel
Function: Recommended for the suspension of non-insulated pipe or insulated pipe with a B3151 shield.
Note: When an oversized clevis is used, a pipe spacer should be placed over the cross bolt to assure that the
lower U-strap will not move in on the bolt. When attaching seismic bracing to the clevis hangers, a B3100PS
(cross bolt spacer) must be installed. See Seismic Restraints Approval Guidelines.
Order pipe sleeves Fig. 1CBS-(pipe size) separately.
Approvals:
Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide
Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to
OSHPD projects, please refer to the B-Line/TOLCO Seismic Restraint Systems Guidelines.
Underwriter's
Laboratories Listed in the USA (UL) and Canada (cUL) for sizes
3
/4” (20mm) thru 12" (300mm). Factory Mutual
Engineering Approved (FM) for
3
/4” (20mm) thru 12” (300mm) pipe.
Conforms to Federal Specification WW-H-171E &
A-A-1192A, Type 1 and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58, Type 1.
Also available to
accommodate rod schedule per per National Fire Protection Association (NFPA) Pamphlet 13.
Maximum Temperature: 650°F
(343°C).
Standard Finish: Plain, Electro-Galvanized, DURA-GREEN
™
, or Hot-Dip Galvanized
also available in Stainless Steel
Order By:
Part
number and finish.
For AWWA - Ductile Iron Clevis Hangers, see B3102, page 51.
** Note: Do not use the dimensions shown in the B3100 chart for NFPA hanger sizes.
Contact B-Line for NFPA rod sizing on
1
/2” (15mm) thru 12” (300mm) pipe.
Part numbers will be 1NFPA-pipe size.
B3100 - Standard Clevis Hanger (TOLCO Fig.1)
*SLIDE-RITE™ Clevis Hanger design, as shown above, for sizes 2, 2
1
/2, 3, 4, 5 & 6.
Component of State of
California OSHPD Approved
Seismic Restraints System
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.