Wiring Diagram

EasyIO FW Series User Reference v3.0
18
Universal Input Connection
EasyIO FW series has non-isolated universal inputs. The universal input supports three type of analog
signal i.e. resistance and voltage via hardware jumper and internal register settings:
Universal Input
8 Channels
Voltage
0 - 10V DC (+/-0.05V)
Resistance
500 - 500K (+/-10 Ohm)
Thermistor
10K, 20K, 1K Balco, 1K Platinum : All (+/-0.1 Deg-C)
UI as Digital Input
Voltage Free Contact
a) Resistance The working range of resistance is 500 Ohm 500k Ohm.
The commonly used Thermistor such as 10K, 20K, 1K Balco and 1K Platinum are all supported.
b) Voltage Supports 0 10V and 0 5V (scaling required).
The minimum input impedance of voltage mode input is 1 Mega Ohm.