Wiring Diagram

EasyIO FW Series User Reference v3.0
17
Analog Output Connection
EasyIO FW series has Analog Output connections. Each Analog Output can only drive voltage.
The operating range for voltage mode is 0 10V.
**We DO NOT recommend you to drive a relay directly from UO 0-10V mode as it is not design for it
and will damaged the UO. **
Universal Output
4 Channels
Type
Voltage: 0 10VDC , Min Impedance 2,000 Ohm.