Operation Manual

10
5. CONFIGURATION OF THE ALARM REGISTERS
5.1 Sensor-1 monitoring
5.1.1 Sensor-1 as alarm contact
EasyAlarm
®
auto-detects a Plug&Protect-sensor and starts its monitoring if the system is armed. You can define the
behaviour for sensor-1 as following:
Example: A normally closed contact shall trigger an un-delayed alarm with a hands-free-connection independent from
position of the selection switch.
1. Slide function switch to PROG
2. Enter sequence *. 9. 3. 1. 7 5 6 #. #.. .
Current register (bit 7 -> bit 0) will be announced followed by “to modify press *., to stop press #.
3. If you want to keep current value proceed with step 6. Otherwise start modifying register by pressing *..
4. Enter sequence 0. 0. 1. 0 0 0. 1. 1. .
R-Siren Entry-Delay Connect. mode Sensor on.. Type
0: off 0:off 0: Listening-in I / II / III 00: inactive
1: on 1:on 1: Hands-free 0 0 0 01: Normally open contact
0: enabled 10: Plug&Protect (auto-detected at power-on)
1: disabled input-2 is open => Normally open monitoring
input-2 is closed => Normally closed monitoring
5. Press key #. . 11: Normally closed contact
The new register (bit 7 -> bit 0) will be announced
6. Slide function switch to OFF
5.1.2 Sensor-1 for presence verification
You can also use sensor-1 to monitor missing activity (i.e. no motion detected within a certain period) => Alarm message:
„Emergency call due to sensor-1“. Therefore you have to activate time-out as below.
5.1.2.1 How to program presence verification time-out
Time-out for presence verification is factory set to 24h. If there is no activation within this period, an alarm is triggered
after a pre warning period of 10 minutes (this period is indicated with a periodical loud beep tone).
1. Shift function switch to PROG
2. Enter *. 9. 7. 1. 3 6 7 #. #. .
Current register value <n> will be announced followed by “to modify press *., to stop press #.
3. If you want to keep current value proceed with step 4. Otherwise modify register with *. New value <n> #..
The new register value <n> will be announced
4. Shift function switch to OFF
<n> Explanation
0 Presence verification is switched off (=Factory setting)
6..255 Time-out in steps of 10 min. (min. 60min, max. 42.5h) => For example: n=144 (144*10min = 24 h)
5.1.3 Sensor-1 as entry-detector (Gong function)
A sensor-1 activity can also be signalled locally (Gong-function) according to the following procedure:
Example: Sensor-1 shall greet an incoming person with the pre-recorded individual message only on position I.
1. Slide function switch to PROG
2. Enter sequence *. 9. 3. 1. 7 3 1 #. #...
Current register (bit 7 -> bit 0) will be announced followed by “to modify press *., to stop press #.
3. If you want to keep current value proceed with step 6. Otherwise start modifying register by pressing *..
4. Enter sequence 0. 0. 0. 0 1 1. 1. 0. .
Unused Gong on.. Gong-type
000: I / II / III 00: Gong
0 1 1 01: --
0: enabled 10: Individual message
1: disabled 11: Beep loud
5. Press key #. .
The new register (bit 7 -> bit 0) will be announced
6. Slide function switch to OFF
Factory default for sensor
-
1 monitoring
00 0 000 10, => un-delayed alarm in listening-in
connection only on all positions I/II/III
=> connector type: auto-type (plug&protect)
Factory default for gong
-
function sensor
-
000 111 00
Note:
If you do not want to
trigger an alarm on
position I you have to
disable alarm according to
section 5.1.1