Programming instructions
7
TIE DOWN STRAPS
The base of the unit may be used to
fasten the unit in accordance with your
local building code. Attach two tie strap
on opposite sides of unit
(See diagram
HS1)
and anchor to the deck.
Above Ground Pool Installations
When installing a heater below the pool level, the manufacture requires an
external flow switch. This is to prevent the pressure switch from falsely
indicating water flow due to high head pressure of the water. Failure to use
an external flow switch may cause the unit to activate without water flow.
The unit may go into “WATER FLOW
LOCKOUT”. Failure to use the
external flow switch may damage
the unit and will void the warranty.
You may install the flow switch on
the inlet or outlet side of the
plumbing. Wire the flow switch into
the space marked WPS located on
the bottom right corner of the
board.
(See Diagram FS1).
Remove
White wires from the Water
Pressure Switch and insert the two
Initial Installation Programming on
Pool/Spa Electronic Control
After completing the plumbing and wiring of the heat pump, “LANGUAGE
SELECT” will appear on the display. Select your desired language, and press
the “MODE” button to get to the “TEMP SCALE” selection. This install menu
will be on the display for 30 Seconds and the display will change to the
Operation Menu. From the Operation Menu you can set the set point.
If the 30 seconds finished and you still need to adjust any of the settings, cut
the power off to the board and turn back on. The board will display the
“LANGUAGE SELECT” screen again for another 30 seconds. The factory
setting is English and ˚F.
!"#$%"&'()#*&'
+%",'(""&'
-"'(""&'