Manual

6 ADKS Owner’s Manual
III. ROOF, GUTTER & DOWNSPOUT
REQUIREMENTS
IV. ELECTRICAL REQUIREMENTS
Is ground-fault protected. A ground-fault protected receptacle reduces
the risk of fire or electric shock by stopping the flow of electricity (current)
when it senses that current is flowing through something other than the
cable (for example, a person or downspout). This unintended current:
can be caused by a damaged cable,
may not be large enough to trip a circuit breaker,
can lead to overheating of the cable, which can result in fire, and
may result in electrocution due to exposed electrical parts.
One type of ground-fault protection is a ground-fault circuit-interrupter
(GFCI). Some, but not all, outdoor receptacles are equipped with a
GFCI.
If you are not sure if your receptacle has ground-fault protection, check
with your local electrical inspector or a licensed electrician, or use the
Easy Heat Heating Cable Protector (HCP1) (sold separately). The Easy
Heat Heating Cable Protector (HCP1) is a ground-fault protection device
that is intended primarily to protect against fire. The HCP1 also provides
some protection against electric shock and electrocution, but it does not
reduce the risk as much as a GFCI.
Is on a circuit that has an appropriate current (amp) rating. Do
not use this cable on a circuit whose circuit breaker or fuse is rated at
more than 20 amps. Limiting the circuit to a maximum of 20 amps will
reduce the risk of fire and electric shock if the cable becomes damaged.
While a 20 amp circuit is the maximum allowed, you also need to check
that the circuit can supply enough current without being overloaded.
Overloading a circuit can lead to a tripped breaker or a blown fuse. To
avoid overloading the circuit, do not use more than 80% of the circuit’s
rated capacity (for example, do not load a 20 amp circuit more than 16
amps, and do not load a 15 amp circuit above 12 amps).
See Table 1 below for the current needed for your cable length. If you do
not have a circuit with an appropriate rating, contact a licensed electrician.
This kit is only designed for use on:
inclined roofs. An inclined roof is one where the water is expected to
flow off the roof edge.
roofs with noncombustible tab shingles (such as asphalt shingles) that
meet national building codes.
metal or plastic gutters/downspouts.
There are several requirements for the electrical system that supplies power to
this deicing cable. Check with your local electrical inspector or a licensed elec-
trician if you are unsure about the requirements listed below or what you may
need to do in order to meet all applicable electrical codes and ordinances.
This cable must be plugged into a 120 volt A/C outdoor receptacle that:
Is grounded. This cable is equipped with a three-prong plug that has a
grounding prong. To reduce the risk of fire and electric shock, this cable
must be grounded. To do this, the plug must be plugged into an outlet that
is properly installed and grounded in accordance with all local electrical
codes and ordinances.
Do not modify the plug provided with the cable. If it will not fit the outlet,
have a proper outlet installed by a licensed electrician.
Do not use this kit on any other type of roof, gutter and downspout, including:
Roofs with wooden shingles.
Rubber or rubber membrane roofs.
Composite (tar and gravel) roofs.
Wooden gutters or downspouts.
Flat roofs.
Slate, stone or ceramic and metal roofs. These types of roofs re-
quire special consideration. Contact Easy Heat for more information
toll-free at 800/562-6587.
If you are unsure if your roof, gutters, and downspouts meet these require-
ments, call a professional roofing contractor.
Table 1 Current Needed for Easy Heat De-Icing Products
Catalog Number Current Needed (Amps)
ADKS-100 0.83
ADKS-150 1.3
ADKS-300 2.5
ADKS-400 3.3
ADKS-500 4.2
ADKS-600 5.0
ADKS-800 6.7
ADKS-1000 8.3
ADKS-1200 10.0
Failure to meet these electrical system requirements
may result in ice dam formation or injury or death from electric
shock or fire.
WARNING
Use of this kit on any other type of roof, gutter or downspout
increases the risk of ice dam formation or injury or death from
electric shock or fire.
WARNING
ENG
ESP
Modelo ADKS guía del usuario 63
VII. UTILIZACIÓN Y MANTENIMIENTO
DEL CABLE
Además de una adecuada instalación, se necesita una utilización adecuada
del cable para mantener una vía de escurrimiento hacia el suelo de la nieve
derretida.
A. VERIFICACIONES DE PRE-TEMPORADA
Al comienzo de la temporada invernal, haga lo siguiente:
Retire cualquier basura combustible del techo,los canalones y las
bajadas de agua, tales como hojas de árboles y pinos, semillas y basura
arrastrada por el viento.
Asegúrese de que el cable no se haya movido de su posición
original. La parte conductora de calor del cable, debe reposar
completamente en el techo y no debe tocarse, cruzarse o
encimarse.
Inspeccione visualmente el cable y la clavija sin retirarlo del
techo. Descontinúe la utilización y retire el cable si hay evidencia
de daño o deterioro incluyendo cortadas, resquebrajaduras,
carbonización del aislante, partes descoloridas o alambres pelados. Si
le parece que hay un problema en una bajada de agua, retire el cable
para inspeccionarlo. Tenga cuidado al retirarlo para evitar daños si se
atora, o frota contra bordes afilados o cortantes.
Si no hay daño presente, conecte el cordón de alimentación al
contacto. Con un espaciador, acomode el cable para formar un
bucle de caída (Véase la Figura 24). El propósito del bucle de caída es
prevenir que el agua escurra hacia el cordón de alimentación y hacia
el contacto.
Pruebe cada uno de los dispositivos de protección contra
las fallas de puesta a tierra (refiérase a las instrucciones del
dispositivo).
Un manejo inadecuado del cable puede dañarlo y provocar la
acumulación de hielo, lesiones y muerte por choque eléctrico
o incendio.
ADVERTENCIA
Bucle
de caída
Figura 24. Haga un bucle de caída cerca del punto de partida
B. ENCENDIDO Y APAGADO DEL CABLE
Durante la temporada invernal, encienda el cable sólo cuando las
condiciones sean favorables a la acumulación de hielo. Sólo se debe poner
en funcionamiento el cable cuando:
La nieve y el hilo del techo se derriten y
La temperatura exterior está entre los 15 ºF y 35 ºF (-9 ºC y 2
ºC). Por debajo de los 15 ºF (-9 ºC), no ocurrirá mucho derretimiento
y en condiciones muy frías, el cable no generará el calor suficiente
para evitar que la nieve derretida se congele. Esto puede provocar la
acumulación de hielo y reenviar el agua hacia adentro de las tejas.
Una vez encendido, se debe apagar el cable cuando las condiciones de
derretimiento y congelamiento de nieve se detengan, por lo general por
encima de los 35 ºF (2 ºC). Se debe mantener apagado el cable hasta que
las condiciones propicias para el derretimiento y congelamiento de nieve
regresen.
El cable funciona correctamente si se utiliza:
un interruptor de ENCENDIDO/APAGADO (con una luz
indicadora), o
un Control para cable descongelante (Modelo RS-2)
(opcional).
El Control para cable descongelante (modelo número RS-2) es un
control detector de humedad y de temperatura que controla el
funcionamiento del cable cuando hay presencia de humedad y la
temperatura baja del punto de congelación. La unidad permanecerá
en funcionamiento hasta que la humedad cese o que la temperatura
esté por encima del punto de congelación. Consulte a su distribuidor
local para mayores detalles.