User manual

31
Instruction Manual
PS 8000 2U Series
EN
Date: 02-09-2012
About the device
PS 8040-60 2U PS 8080-60 2U PS 8360-15 2U PS 8040-120 2U
Mains input
Input voltage range 90…264V AC 90…264V AC 90…264V AC 180…264V AC
- with derating 90...150V AC 90...150V AC 90...150V AC 180...207V AC
Input current at 230V max. 7.5A max. 7.5A max. 7.5A max. 15A
Input current at 100V max. 11.4A max. 11.4A max. 11.4A -
Input frequency 45…65Hz 45…65Hz 45…65Hz 45…65Hz
Input fuse T 16A T 16A T 16A T 16A
Power factor > 0.99 > 0.99 > 0.99 > 0.99
Output - Voltage
0 0 0 0
Nominal voltage U
Nom
40V 80V 360V 40V
Adjustable range
0V…U
Nom
0V…U
Nom
0V…U
Nom
0V…U
Nom
Stability at mains fluctuation ±10% U
IN
< 0.02% < 0.02% < 0.02% < 0.02%
Stability at 0…100% load < 0.05% < 0.05% < 0.05% < 0.05%
Ripple @ BWL 20MHz
< 10mV
pp
< 4mV
RMS
< 10mV
pp
< 4mV
RMS
< 50mV
pp
< 8mV
RMS
< 10mV
pp
< 5mV
RMS
Accuracy* 0.2% 0.2% 0.2% 0.2%
Resolution of display 10mV 10mV 100mV 10mV
Remote sense compensation max. 2.5V max. 2.5V max. 8V max. 2.5V
Overvoltage protection
threshold (adjustable)
0….44V 0….88V 0…396V 0….44V
Output - Current
Nominal current I
Nom
60A 60A 15A 120A
Adjustable range
0…I
Nom
0…I
Nom
0…I
Nom
0…I
Nom
Stability at mains fluctuation ±10% U
IN
< 0.05% < 0.05% < 0.05% < 0.05%
Stability at 0…100% U
OUT
< 0.15% < 0.15% < 0.15% < 0.15%
Ripple @ BWL 20MHz
< 19mA
pp
< 7mA
RMS
< 19mA
pp
< 7mA
RMS
< 1mA
pp
< 0.45mA
RMS
< 25mA
pp
< 9mA
RMS
Accuracy* 0.2% 0.2% 0.2% 0.2%
Resolution of display 10mA 10mA 10mA 100mA
Transient recovery time 10….90% load < 2ms < 2ms < 2ms < 2ms
Output - Power
Nominal power P
Nom
1500W 1500W 1500W 3000W
Nominal power at derating 1000W 1000W 1000W 2500W
Accuracy*
0...P
Nom
0...P
Nom
0...P
Nom
0...P
Nom
Adjustable range 1% 1% 1% 1%
Resolution of adjustment 1W 1W 1W 1W
Efficiency max. 93.0% 93.0% 93.0% 93.0%
Miscellaneous
Ambient temperature 0….40°C 0….40°C 0….40°C 0….40°C
Storage temperature -20….70°C -20….70°C -20….70°C -20….70°C
Humidity rel. < 80% < 80% < 80% < 80%
Dimensions normal (WxHxD) 19" 2U 460mm 19" 2U 460mm 19" 2U 460mm 19" 2U 460mm
Dimensions with option ZH (WxHxD) 19" 2U 460mm 19" 2U 460mm 19" 2U 460mm 19" 4U 460mm
Weight normal 11.5kg 11.5kg 11.5kg 14.7kg
Weight with option ZH 13kg 13kg 13kg 17kg
Isolation +output<->enclosure 500V 500V 500V 500V
Isolation -output<->enclosure
Isolation input<->output
Cooling
Standards
Overvoltage class
Protection class
Pollution degree
Operation altitude
Series connection
max. series connection voltage
Master-Slave
Parallel connection
max. parallel connection voltage
Master-Slave
Analogue programming
Input range
Accuracy
Article numbe
r
09230144 09230134 09230137 09230145
300V DC
yes, via Share bus
1
2
< 2000m
0…5V or 0…10V, selectable
<
0.2%
600V
no
720V
4200V
by fans, air inlets on the front, air exhaust on the rear
EN 60950, EN 61326, EN 55022 Class B
2
* Related to the nominal value, the accuracy denes the maximum allowed deviation between set value and actual value.
Example: a 80V model has min. 0.2% voltage accuracy. This is 160mV. When setting a voltage of 5V and with an allowed maximum deviation of 160mV, the resulting
actual value could be between 4.84V and 5.16V.