User manual
10
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
© 2009, Elektro-Automatik GmbH & Co. KG
For coarse adjustment, following step widths apply in dependency
of the nominal values (also refer to technical specs):
Voltage Current
Nom. value Step width Nom. value Step width
16V 0.1V 4A 50mA
32V 0.2V 5A 50mA
65V 0.5V 10A 0.1A
80V 0.5V 15A 0.1A
160V 1V 20A 0.2A
360V 2V 40A 0.5A
60A 0.5A
Important! The resolution of the adjustable set values is, at some
models, higher than the one of the output voltage. Thus it can hap-
pen that the output voltage only changes every 2 or 3 steps.
2. Remote control by analogue interface
The analogue interface (AI) allows to remotely control current and
voltage, always in combination. It means, that it‘s not possible to
adjust voltage by the AI and the current with the rotary encoder on
the front at the same time, or vice versa. Because the OVP thres-
hold can not be adjusted via the AI, it‘s required to set it manually
on the device before using the remote control. Switching to preset
mode with the pushbutton Preset V/C/OVP shows the translated
set values, that are put into the set value pins of the AI as voltages.
In order to put in the appropriate set values, the user can either use
an external voltage or the reference output voltage on pin 3.
In case it is only required to adjust voltage by external means, the
current set value (CSEL) can be bridged to the reference voltage
(VREF).
The AI can be operated with the common 0...5V or 0...10V ran-
ges, each corresponding to 0...100% nominal values. The desired
voltage range is selected in the device setup (see section „Device
setup“). Following applies:
0-5V: Reference voltage = 5V, 0...5V set value voltage correspond
to 0...100% nominal value, 0...100% actual value correspond to
0...5V at the actual value outputs.
0-10V: Reference voltage = 10V, 0...10V set value voltage corre-
spond to 0...100% nominal value, 0...100% actual value correspond
to 0...10V at the actual value outputs.
Putting in set values that exceed the limit, for example >5V while the
0...5V range is selected, is intercepted by clipping the concerning
set value to 100% .
Never input voltages higher than 12V to the set value inputs!
3. Remote control by digital interface
The digital interfaces allow to set voltage and current, as well as
the OVP threshold by means of a PC. When changing to remote
control mode, the device keeps the last set values until they‘re
altered. Hence it would be possible to control only voltage by sen-
ding arbitrary set values and the current set value would remain
unaltered.
Set values given by the digital interface (except GPIB) are always
percentage and correspond at 100% (hex: 0x6400), resp. at 110%
(hex: 0x6E00) for the OVP threshold, to the nominal values of the
device.
Furthermore, the digital interfaces allow to query and set a lot
of other features and values. For details refer to section „Digital
interface cards“ and the user manual of the IF cards.
7. Behaviour when...
7.1 Switching on by power switch
The power switch is located at the rear. After switching the device
on it is immediately ready to work. In the device setup (see section
„Device setup“) is an option named „P on“, which stands for auto
power on, that determines the state of the power output when the
device is switched on. By default, this is option is set to on, meaning
that the device will save the last output condition, including the set
values, when it is switched off by the power switch and restore the
condition after the next start.
If the option is set to „off“, the set values of U and I are set to 0 and
the output is switched on after the next start.
7.2 Switching off by power switch
Switching the device by power switch is handled as mains blackout.
The device will save the last set values and output condition. After
a short time, power output and fan will be switched off and after a
few seconds more, the device will be completely off.
7.3 Switching on or off by standby button
Same behaviour as when switched on or off by power switch. The
condition is restored or not, according to the setting „P on“ in the
device setup.
7.4 Switching to remote control
a) Analogue interface: Pin „Remote“ switches the device to remote
control, done via the set values pins VSEL and CSEL, as well as
REM-SB. The output condition and the set values which are put
into pins 1, 2 and 13 (also see section „Analogue interface“) are
immediately set. After return from remote control into manual con-
trol, the output will be switched off and the last remotely adjusted
set values of U and I are kept.
b) Digital interface: Switching to remote control by the corresponding
command (here: object) keeps output state and set values until
altered. Returning from remote control switches the output off and
the last, remotely adjusted set values of U and I are kept.
7.4 Overvoltage occurs
An overvoltage error can occur due to an internal defect (output
voltage rises uncontrolled) or by a too high voltage from external.
The overvoltage protection (OVP) will switch off the output and
indicate the error by the LED „OVP“.
External voltages higher than 120% nominal voltage at the
output must be avoided, or else internal components of the
device might be destroyed!
If the cause of the overvoltage is removed, the output can be swit-
ched on again and the LED „OVP“ will go out. In manual operation,
this is done by pushing button Output On and in analogue remote
control with pin „REM-SB“. If the error is still present, the output
can not be switched on.
OVP errors are recorded as alarm into the internal alarm buffer.
This buffer can be read out via the digital interface.
Operating the device