User manual

Page 14
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
ea1974@elektroautomatik.de
PS 3000 C Series
640 W
Model
PS 3040-40 C PS 3080-20 C PS 3200-10 C
Power regulation
Display: Resolution See section „1.9.5.4. Resolution of the displayed values“
Display: Accuracy
(1
≤0,5%P
Nenn
≤0,5%P
Nenn
≤0,5%P
Nenn
Analog interface (optional)
(2
Set value inputs U, I, P
Actual value output U, I
Control signals DCon/o,remotecontrolon/o
Status signals CV, OVP, OT
Galvanic isolation to the device Max. 1500 V
DC
Sample rate of inputs & outputs Max. 100 Hz
Insulation
Output (DC) to enclosure (PE)
DC minus: permanent max. ±400 V
DC plus: permanent max. ±400V + output voltage
Input (AC) to output (DC) Max. 2500 V, short-term
Miscellaneous
Cooling Temperature controlled fan, side inlet, rear exhaust
Ambient temperature 0..50°C
Storage temperature -20...70°C
Humidity < 80%, not condensing
Standards EN 61010, EN 60950
Overvoltage category 2
Protection class 1
Pollution degree 2
Operational altitude < 2000 m
Digital interfaces
Optionally available
IF-KE5USB:1xUSB
IF-KE5USBLAN:1xUSB+1xLAN
IF-KE5USBANALOG:1xUSB+1xAnalog
Galvanic isolation from device Max. 1500 V
DC
Terminals
Rear side AC input, analog interface (optional), USB (optional), Ethernet (optional)
Front side DC output, USB-A, remote sensing
Dimensions
Enclosure (WxHxD) 260 x 88 x 350 mm
Total (WxHxD) 308 x min. 103 x min. 359 mm
Weight ~ 5 kg ~ 5 kg ~ 5 kg
Article number 35320214 35320215 35320216
(1Relatedtothenominalvalues,theaccuracydenesthemaximumdeviationbetweenanadjustedvaluesandthetrue(actual)value.
(2 The display error adds to the error of the related actual value on the DC output
(3Fortechnicalspecicationsoftheanaloginterfacesee„3.5.4.4 Analog interface specication“ on page 42