User manual

Page 11
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
ea1974@elektroautomatik.de
EL 9000 T Series
(1Optionallyavailable,fortechnicalspecicationsoftheanaloginterfacesee„3.5.4.4 Analog interface specication“ on page 41
Model
EL 9080-45 T EL 9200-18 T EL 9500-08 T
Analog interface
(1
Set value inputs U, I, P, R
Actual value output U, I
Control signals DC on/off, Remote on/off, R mode on/off
Status signals CV, OVP, OT
Galvanic isolation to the device max. 1500 V DC
Sample rate (set value inputs) 500 Hz
Insulation
Input (DC) to enclosure
DC minus: permanent max. 400 V
DCplus:permanentmax.400V+max.inputvoltage
Input (AC) to input (DC) Max. 2500 V, short-term
Environment
Cooling Temperature controlled fans
Ambient temperature 0..50 °C
Storage temperature -20...70 °C
Digital interfaces
Featured 1x USB-B for communication (rear side), 1x USB-A for functions (front side)
Optional 1x LAN for communication (front side)
Galvanic isolation to the device max. 1500 V DC
Terminals
Rear side AC input, USB-B, Ethernet (optional), analog interface (optional)
Front side DC input, USB-A, remote sensing
Dimensions
Enclosure (WxHxD) 92 x 239 x 352 mm
Total (WxHxD) 92 x 239 x min. 393 mm
Standards EN 60950
Weight ~ 6.5 kg ~ 6.5 kg ~ 6.5 kg
Article number 33210511 33210512 33210513