3.3.6 Share bus fail
A Share bus fail alarm (short: SF) will switch off the DC power stage and can occur if
• the Share bus connectors of at least two units are already wired while at least one unit isn’t yet congured for master-slave
• a short-circuit on the Share bus has occurred, for example due to a damaged BNC cable.
This function serves to prevent sending irregular control signals to the slave units via the Share bus or to cause them to react
differently. This alarm has to be acknowledged after the cause has been removed. Should the device neither be master nor
slave, the Share bus cable should be removed for unimpeded operation.