Manual

Table Of Contents
© EA Elektro-Automatik in 2022, this information is subject to change without notice 2733200840_manual_elr_10000_2u_3kw_en_02
2. Installation & commissioning
2 .1 Transport and storage
2 .1.1 Transpor t
• The handles on the front and rear side of the device are not for carrying!
• Do not transport when switched on or connected!
• When relocating the equipment use of the original packing is recommended
• The device should always be carried and mounted horizontally
2 .1.2 Packaging
Its recommended to keep the complete transport packaging for the lifetime of the device for relocation or return to the man-
ufacturer for repair. Otherwise the packaging should be disposed of in an environmentally friendly way.
2 .1.3 Storage
In case of long term storage of the equipment its recommended to use the original packaging or similar. Storage must be in
dry rooms, if possible in sealed packaging, to avoid corrosion, especially internal, through humidity.
2.2 Unpacking and visual check
After every transport, with or without packaging, or before commissioning, the equipment should be visually inspected for
damage and completeness using the delivery note and/or parts list (see section
“1.9.3. Scope of delivery
). An obviously
damaged device (e.g. loose parts inside, damage outside) must under no circumstances be put in operation.
2.3 Installation
2.3.1 Safety procedures before installation and use
• When using a 19” rack, rails suitable for the width of the housing and the weight of the device are to be
used (see
“1.8. Technical Data
• Before connecting to the mains ensure the supply voltage is as shown on the product label. Overvoltage
on the AC supply can cause equipment damage.
• Devices of this series feature an energy recovery function which, similar to solar energy equipment, which
feeds energy back into the local or public grid. Feedback into the public grid must not be operated without
adherence of directives from the local energy supplying company and it must be investigated before the
installation or latest before initial commission if there is requirement to install a grid protection device!
2.3.2 Preparation
2.3.2.1 Selecting cables
The required AC supply connection for these device is termination. Its done via the 3 pole clamp terminal on the rear (AC lter
box). Wiring of the terminal requires a 3 wire (L, N, PE) cable of suitable cross section and length (not included in delivery).
For recommendations for a cable cross section see
“2.3.4. Connection to AC supply.
Dimensioning of the DC wiring to the
source has to reect the following:
• The cable cross section should always be specied for at least the maximum current of the device.
• Continuous operation at the approved limit generates heat which must be removed, as well as voltage
loss which depends on cable length and heating. To compensate for these the cable cross section should
be increased and the cable length reduced.