Manual

Table Of Contents
© EA Elektro-Automatik in 2022, this information is subject to change without notice 2533200840_manual_elr_10000_2u_3kw_en_02
1.9.9 Analog interface
This 15 pole D-sub socket on the rear side of the device is provided for remote control
of the device via analog or digital signals.
If remote control is in operation this analog interface can only be used alternately to the
digital interface. However, monitoring is always available.
The input voltage range of the set values and the output voltage range of the monitor
values, as well as reference voltage level can be switched in the settings menu of the
device between 0-5 V and 0-10 V, in each case for 0-100%.
Figure 4 - Analog interface
1.9 .10 “Share BUS” connector
The two BNC sockets (50 Ω type) labeled “Share BUS” form a digital, passed-through
Share bus. This bus is bidirectional and connects the bus master unit via “Share BUS
Output” to the next slave unit (“Share BUS Input”) etc., for use in parallel operation (mas-
ter-slave). BNC cables of suitable length can be obtained from us or electronics stores.
Basically, all 10000 series are compatible on this Share bus, though only connection
of the same device type, i. e. power supply with power supply or electronic load with
electronic load is supported by the devices for master-slave.
For an ELR 10000 device only different or identical ELR 10000 models can be used as
slave units.
Figure 5 - Share bus
1.9 .11 “Sense” connector (remote sensing)
In order to compensate for voltage drops along the DC cables external source, the
Sense input (2 plugs included in delivery, one each for positive and negative pole) can
be connected to the external source. The maximum possible compensation is given in
the technical specications.
In a master-slave system its intended to wire remote sensing only
to the master which would then forward the compensation to the
slaves via Share BUS.
The Sense cover must be installed during operation, because
there can be hazardous voltage on the sense lines! Recongu-
ration on the Sense terminals is only permissible if the device is
disconnected from AC supply and all DC sources!
Figure 6 - Remote sensing terminals