User manual
Page 10
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
ea1974@elektroautomatik.de
EL 9000 B HP Series
1.8.3 Specic technical data
(1Inrelationtoaratedvalues,theaccuracydenesthemaximumdeviationbetweenasetvalueandthecorrespondingactualvalue
Example: the 85 A model has min. 0.2% current accuracy, that is 170 mA. When adjusting the current to 10 A, the actual value is allowed to differ max. 170 mA,
which means it is allowed to be between 9.83 A and 10.17 A.
(2 Up to 30°C ambient temperature, but less above this point and with continuous derating
(3 The accuracy or max. error of a value on display adds to the error of the actual value on the DC input
Up to 1200 W
Model HP
EL 9080-85 B EL 9200-35 B EL 9360-20 B EL 9500-15 B EL 9750-10 B
AC mains supply
Supply voltage 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC
Connection type Wall socket Wall socket Wall socket Wall socket Wall socket
Frequency 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz
Fuse T 6.3 A T 6.3 A T 6.3 A T 6.3 A T 6.3 A
Power consumption max. 45 W max. 45 W max. 45 W max. 45 W max. 45 W
Leak current < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA
DC Input
Max. input voltage U
Max
80 V 200 V 360 V 500 V 750 V
Input power P
Max
(2
1200 W 1000 W 900 W 600 W 600 W
Max. input current I
Max
85 A 35 A 20 A 15 A 10 A
Overvoltage protection range 0...1.03 * U
Max
0...1.03 * U
Max
0...1.03 * U
Max
0...1.03 * U
Max
0...1.03 * U
Max
Overcurrent protection range 0...1.1 * I
Max
0...1.1 * I
Max
0...1.1 * I
Max
0...1.1 * I
Max
0...1.1 * I
Max
Overpower protection range 0...1.1 * P
Peak
0...1.1 * P
Peak
0...1.1 * P
Peak
0...1.1 * P
Peak
0...1.1 * P
Peak
Max. allowed input voltage 88 V 220 V 396 V 550 V 825 V
Min. input voltage for I
Max
approx. 2.2 V approx. 2 V approx. 2 V approx. 6.5 V approx. 5.5 V
Temperaturecoefcientforset
valuesΔ/K
Voltage / current: 30 ppm
Voltage regulation
Adjustment range 0...80 V 0...200 V 0...360 V 0...500 V 0...750 V
StabilityatΔI < 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Accuracy
(1
(at 23 ± 5°C) ≤0.1%U
Max
≤0.1%U
Max
≤0.1%U
Max
≤0.1%U
Max
≤0.1%U
Max
Display: Adjustment resolution see section „1.9.5.4. Resolution of the displayed values“
Display: Accuracy
(3
≤0.1%
Remote sensing compensation max. 5% U
Max
Current regulation
Adjustment range 0...85 A 0...35 A 0...20 A 0...15 A 0...10 A
StabilityatΔU < 0.1% I
Max
< 0.1% I
Max
< 0.1% I
Max
< 0.1% I
Max
< 0.1% I
Max
Accuracy
(1
(at 23 ± 5°C) ≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
≤0.2%I
Max
Display: Adjustment resolution see section „1.9.5.4. Resolution of the displayed values“
Display: Accuracy
(3
≤0.1%
Rise time 10...90% I
Nom
<23μs <40μs <24μs <22μs <18μs
Fall time 90...10% I
Nom
<46μs <42μs <38μs <29μs <40μs
Power regulation
Adjustment range 0…P
Max
0…P
Max
0…P
Max
0…P
Max
0…P
Max
Accuracy
(1
(at 23 ± 5°C) < 0.5% P
Max
< 0.5% P
Max
< 0.5% P
Max
< 0.5% P
Max
< 0.5% P
Max
Display: Adjustment resolution see section „1.9.5.4. Resolution of the displayed values“
Display: Accuracy
(3
≤0.2%P
Max
Resistance regulation
Adjustment range 0.08…30Ω 0.44…200Ω 1.4…600Ω 2.5…1200Ω 6…2500Ω
Accuracy
(at 23 ± 5°C) ≤1%ofmaximumresistance+0.3%ofmaximumcurrent
Display: Adjustment resolution see section „1.9.5.4. Resolution of the displayed values“
Display: Accuracy
(3
≤0.2%