Elektro-Automatik Betriebsanleitung EL 9000 B HP Elektronische DC-Last Doc ID: EL9HDE Revision: 01 Date: 04/2017
EL 9000 B HP Serie INHALT 1 ALLGEMEINES 1.1 1.1.1 1.1.2 1.1.3 1.1.4 1.2 1.3 1.4 1.5 1.6 1.7 1.7.1 1.7.2 1.7.3 1.7.4 1.7.5 1.8 1.8.1 1.8.2 1.8.3 1.8.4 1.8.5 1.9 1.9.1 1.9.2 1.9.3 1.9.4 1.9.5 1.9.6 1.9.7 1.9.8 1.9.9 1.9.10 1.9.11 2 Zu diesem Dokument.....................................5 Aufbewahrung und Verwendung....................5 Urheberschutz (Copyright).............................5 Geltungsbereich..............................................5 Symbole und Hinweise................................
EL 9000 B HP Serie 3.10.5 3.10.6 3.10.7 3.10.8 3.10.9 3.10.10 3.10.11 3.10.12 3.10.13 3.10.14 3.10.15 3.11 3.11.1 3.11.2 3.11.3 Sinus-Funktion..............................................62 Dreieck-Funktion...........................................62 Rechteck-Funktion........................................63 Trapez-Funktion............................................64 DIN 40839-Funktion.....................................64 Arbiträr-Funktion...........................................
EL 9000 B HP Serie 1. Allgemeines 1.1 Zu diesem Dokument 1.1.1 Aufbewahrung und Verwendung Dieses Dokument ist für den späteren Gebrauch und stets in der Nähe des Gerätes aufzubewahren und dient zur Erläuterung des Gebrauchs des Gerätes. Bei Standortveränderung und/oder Benutzerwechsel ist dieses Dokument mitzuliefern und bestimmungsgemäß anzubringen bzw. zu lagern. 1.1.
EL 9000 B HP Serie 1.4 Entsorgung des Gerätes Ein Gerät, das zur Entsorgung vorgesehen ist, muß laut europaweit geltenden Gesetzen und Verordnungen (ElektroG, WEEE) von Elektro-Automatik zurückgenommen und entsorgt werden, sofern der Betreiber des Gerätes oder ein von ihm Beauftragter das nicht selbst erledigt. Unsere Geräte unterliegen diesen Verordnungen und sind dementsprechend mit diesem Symbol gekennzeichnet: 1.
EL 9000 B HP Serie 1.7 Sicherheit 1.7.1 Sicherheitshinweise Lebensgefahr - Gefährliche Spannung • Beim Betrieb elektrischer Geräte stehen zwangsweise bestimmte Teile unter teils gefährlicher Spannung.
EL 9000 B HP Serie 1.7.3 Pflichten des Betreibers Betreiber ist jede natürliche oder juristische Person, die das Gerät nutzt oder Dritten zur Anwendung überläßt und während der Nutzung für die Sicherheit des Benutzers, des Personals oder Dritter verantwortlich ist. Das Gerät wird im gewerblichen Bereich eingesetzt. Der Betreiber des Gerätes unterliegt daher den gesetzlichen Pflichten zur Arbeitssicherheit.
EL 9000 B HP Serie 1.7.5 Alarmsignale Das Gerät bietet verschiedene Möglichkeiten der Signalisierung von Alarmsituationen, jedoch nicht von Gefahrensituationen. Die Signalisierung kann optisch (auf der Anzeige als Text), akustisch (Piezosummer) oder elektronisch (Pin/Meldeausgang an einer analogen Schnittstelle) erfolgen. Alle diese Alarme bewirken die Abschaltung des DC-Eingangs.
EL 9000 B HP Serie 1.8.3 Spezifische technische Daten Modell HP Bis 1200 W EL 9080-85 B EL 9200-35 B EL 9360-20 B EL 9500-15 B EL 9750-10 B Netzspannung 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC Netzanschluß Steckdose Steckdose Steckdose Steckdose Steckdose Netzfrequenz 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz Netzsicherung T 6,3 A T 6,3 A T 6,3 A T 6,3 A T 6,3 A Leistungsaufnahme max. 45 W max. 45 W max. 45 W max. 45 W max.
EL 9000 B HP Serie Modell HP Bis 1200 W Analoge Schnittstelle EL 9080-85 B EL 9200-35 B EL 9360-20 B EL 9500-15 B EL 9750-10 B (1 Sollwerteingänge U, I, P, R Istwertausgänge U, I Steuersignale DC ein/aus, Fernsteuerung ein/aus, R-Modus ein/aus Meldesignale CV, OVP, OT Galvanische Trennung zum Gerät max. 1500 V DC Abtastrate Sollwerteingänge 500 Hz Isolation Eingang (DC) zum Gehäuse Eingang (AC) to Eingang (DC) DC-Minus: dauerhaft max. ±400 V DC-Plus: dauerhaft max. ±400 V + max.
EL 9000 B HP Serie Modell HP Bis 2400 W EL 9080-170 B EL 9200-70 B EL 9360-40 B EL 9500-30 B EL 9750-20 B Netzspannung 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC Netzanschluß Steckdose Steckdose Steckdose Steckdose Steckdose Netzfrequenz 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz Netzsicherung T 6,3 A T 6,3 A T 6,3 A T 6,3 A T 6,3 A Leistungsaufnahme max. 45 W max. 45 W max. 45 W max. 45 W max.
EL 9000 B HP Serie Modell HP Bis 2400 W Analoge Schnittstelle EL 9080-170 B EL 9200-70 B EL 9360-40 B EL 9500-30 B EL 9750-20 B (1 Sollwerteingänge U, I, P, R Istwertausgänge U, I Steuersignale DC ein/aus, Fernsteuerung ein/aus, R-Modus ein/aus Meldesignale CV, OVP, OT Galvanische Trennung zum Gerät max. 1500 V DC Abtastrate Sollwerteingänge 500 Hz Isolation Eingang (DC) zum Gehäuse Eingang (AC) to Eingang (DC) DC-Minus: dauerhaft max. ±400 V DC-Plus: dauerhaft max. ±400 V + max.
EL 9000 B HP Serie Ansichten A - Netzschalter B - Bedienteil C - Steuerungsschnittstellen (digital, analog) D - Share-Bus- und Fernfühlungsanschlüsse G - Master-Slave-Anschlüsse E - DC-Eingang (Schraubanschluß für M6-Schrauben) F - Netzanschluß 1.8.4 Bild 1 - Vorderansicht EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Bild 2 - Rückansicht Telefon: 02162 / 3785-0 Telefax: 02162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.
EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Telefon: 02162 / 3785-0 Telefax: 02162 / 16230 Bild 4 - Seitenansicht von rechts, ohne DC-Abdeckung Bild 3 - Seitenansicht von links, mit DC-Abdeckung EL 9000 B HP Serie www.elektroautomatik.de ea1974@elektroautomatik.
EL 9000 B HP Serie Bild 5 - Ansicht von oben EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Telefon: 02162 / 3785-0 Telefax: 02162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.
EL 9000 B HP Serie 1.8.5 Bedienelemente Bild 6- Bedienfeld Übersicht der Bedienelemente am Bedienfeld Für eine genaue Erläuterung siehe Abschnitte „1.9.5. Die Bedieneinheit (HMI)“.
EL 9000 B HP Serie 1.9 Aufbau und Funktion 1.9.1 Allgemeine Beschreibung Das „HP“ in der Serienbezeichnung EL 9000 B HP steht für „High Power“ und weist auf verbesserte Eigenschaften in Bezug auf die bei konventionellen Lasten typische thermische Leistungsbegrenzung (engl. derating) hin. Bei der HP-Serie definiert sich die maximale Leistung bis 30 °C Umgebungstemperatur, im Vergleich zur Serie EL 9000 B wo es 25 °C sind.
EL 9000 B HP Serie 1.9.3 Lieferumfang 1 x Elektronische Last 1 x Stecker für Share-Bus 1 x Stecker für Fernfühlung 2 x Füllstreifen (Verwendung siehe 2.3.3.1) 1 x USB-Kabel 1,8 m 1 x Set DC-Klemmenabdeckung 1 x USB-Stick mit Dokumentation und Software 1 x Netzkabel (IEC, Schuko, 10 A) 1.9.4 Zubehör Für diese Geräte gibt es folgendes Zubehör: Digitale Schnittstellenmodule Steck- und nachrüstbare Schnittstellenmodule für RS232, CANopen, Ethernet, Profibus, ProfiNet, ModBus TCP oder CAN sind erhältlich.
EL 9000 B HP Serie 1.9.5 Die Bedieneinheit (HMI) HMI steht für Human Machine Interface, aut deutsch Mensch-Maschine-Schnittstelle. Es besteht aus einer Anzeige mit berührungsempfindlicher Oberfläche (Touchscreen), zwei Drehknöpfen, einem Taster und einem USB-Port Typ A. 1.9.5.1 Anzeige mit Touchscreen Die grafische Anzeige mit Touchscreen ist in mehrere Bereiche aufgeteilt.
EL 9000 B HP Serie • Statusanzeigen (oben rechts) Dieses Feld zeigt diverse Statustexte und -symbole an: Anzeige Beschreibung Gesperrt Das HMI ist gesperrt Entsperrt Das HMI ist nicht gesperrt Fern: Das Gerät befindet sich in Fernsteuerung durch... Analog ...die eingebaute Analogschnittstelle USB & andere ...
EL 9000 B HP Serie 1.9.5.4 Auflösung der Anzeigewerte In der Anzeige können Sollwerte in festen Schrittweiten eingestellt werden. Die Anzahl der Nachkommastellen hängt vom Gerätemodell ab. Die Werte haben 4 oder 5 Stellen. Ist- und Sollwerte haben die gleiche Stellenanzahl.
EL 9000 B HP Serie 1.9.6 USB-Port Typ B (Rückseite) Der USB-Port Typ B auf der Rückseite des Gerätes dient zur Kommunikation mit dem Gerät, sowie zur Firmwareaktualisierung. Über das mitgelieferte USB-Kabel kann das Gerät mit einem PC verbunden werden (USB 2.0, USB 3.0). Der Treiber wird auf USB-Stick mitgeliefert und installiert einen virtuellen COM-Port. Das Gerät kann über diesen Port wahlweise über das international standardisierte ModBus-Protokoll oder per SCPI-Sprache angesprochen werden.
EL 9000 B HP Serie 1.9.9 Share-Bus-Anschluß Die auf der Rückseite des Gerätes befindliche, 2polige Buchse („Share“) dient zur Verbindung mit der gleichnamigen Buchse an kompatiblen elektronischen Lasten zwecks Parallelschaltung und Stromsymmetrierung, sowie an kompatiblen Netzgeräten zwecks Herstellung eines Zwei-Quadranten-Betriebs. Mehr dazu siehe „3.11.3. Zwei-Quadranten-Betrieb (2QB)“.
EL 9000 B HP Serie 2. Installation & Inbetriebnahme 2.1 Transport und Lagerung 2.1.1 Transport • Die Griffe an der Vorderseite des Gerätes dienen nicht zum Tragen! • Das Gerät sollte aufgrund seines Gewichts möglichst nicht per Hand transportiert werden bzw.
EL 9000 B HP Serie 2.3.2 Vorbereitung Für den netzseitigen Anschluß der elektronischen Lasten der Serie EL 9000 B HP ist eine typische Wandsteckdose ausreichend. Das dazu benötigte Netzkabel ist im Lieferumfang enthalten. Durch die relativ geringe Stromaufnahme, selbst bei Betrieb unter Vollast, sind keine weiteren Maßnahmen nötig. Die Geräte können daher auch zusammen mit andersartigen Geräten an einer Verteilersteckdose betrieben werden. 2.3.
EL 9000 B HP Serie 2.3.4 Anschließen von DC-Quellen Bei einem Gerät mit hohem Nennstrom und demzufolge entsprechend dicken und schweren DC-Anschlußleitungen sind das Gewicht der Leitungen und die Belastung des DC-Anschlusses am Gerät zu beachten und besonders bei Installation des Gerätes in einem 19"-Schrank oder ähnlich, wo die Leitungen am DC-Eingang hängen, Zugentlastungen anzubringen. Der DC-Lasteingang befindet sich auf der Rückseite des Gerätes und ist nicht über eine Sicherung abgesichert.
EL 9000 B HP Serie 2.3.5 Erdung des DC-Eingangs Grundsätzlich kann das Gerät am DC-Minuspol geerdet, sprich direkt mit PE verbunden werden. Beim DC-Pluspol ist das anders. Hier gilt: wenn geerdet werden soll, dann nur bis 400 V Eingangsspannung, weil das Potential des DC-Minuspols dann um den Betrag der Eingangsspannung negativ verschoben würde. Daher ist bei Modellen, die mehr als 400 V Eingangsspannung vertragen, die Erdung des DC-Pluspols aus Sicherheitsgründen nicht zulässig.
EL 9000 B HP Serie 2.3.8 Anschließen des USB-Ports (Rückseite) Um das Gerät über diesen Anschluß fernsteuern zu können, verbinden Sie Gerät und PC über das mitgelieferte USB-Kabel und schalten Sie das Gerät ein, falls noch ausgeschaltet. 2.3.8.1 Treiberinstallation (Windows) Bei der allerersten Verbindung mit dem PC sollte das Betriebssystem das Gerät als neu erkennen und einen Treiber installieren wollen.
EL 9000 B HP Serie 2.3.10 Anschließen der analogen Schnittstelle Der 15polige Anschluß (Typ: Sub-D) auf der Rückseite ist eine analoge Schnittstelle. Um diese mit einer steuernden Hardware (PC, elektronische Schaltung) zu verbinden, ist ein handelsüblicher Sub-D-Stecker erforderlich (nicht im Lieferumfang enthalten). Generell ist es ratsam, bei Verbindung oder Trennung dieses Anschlusses das Gerät komplett auszuschalten, mindestens aber den DC-Eingang.
EL 9000 B HP Serie 3. Bedienung und Verwendung 3.
EL 9000 B HP Serie 3.2.2 Stromregelung / Konstantstrom / Strombegrenzung Stromregelung wird auch Strombegrenzung oder Konstantstrom-Betrieb (kurz: CC) genannt und spielt eine wichtige Rolle im Normalbetrieb einer elektronischen Last.
EL 9000 B HP Serie Prinzipdarstellung des Derating-Verlaufs: Ab ca. 30°C Umgebungstemperatur startet das temperaturabhängige Derating mit kontinuierlicher Absenkung der aufnehmbaren Leistung. Der Arbeitstemperaturbereich der Lasten ist bis 50°C Umgebung definiert. Oberhalb dieses Punktes kann jederzeit eine Übertemperaturabschaltung (OT) stattfinden, was jedoch aufgrund des kontinuierlichen Deratings erst oberhalb von 80°C auftreten sollte, wenn überhaupt. P Nennleistung 10°C 3.2.
EL 9000 B HP Serie 3.3 Alarmzustände Dieser Abschnitt gibt nur eine Übersicht über mögliche Alarmzustände. Was zu tun ist im Fall, daß Ihr Gerät Ihnen einen Alarm anzeigt, wird in Abschnitt „3.6. Alarme und Überwachung“ erläutert. Grundsätzlich werden alle Alarmzustände optisch (Text + Meldung in der Anzeige), akustisch (wenn Alarmton aktiviert) und als auslesbarer Status, sowie Alarmzähler über digitale Schnittstelle signalisiert.
EL 9000 B HP Serie 3.4 Manuelle Bedienung 3.4.1 Einschalten des Gerätes Das Gerät sollte möglichst immer am Netzschalter (Vorderseite) eingeschaltet werden. Alternativ kann es über eine externe Trennvorrichtung (Hauptschalter, Schütz) mit entsprechender Strombelastbarkeit netzseitig geschaltet werden. Nach dem Einschalten zeigt es in der Anzeige für einige Sekunden das Herstellerlogo und weitere Geräteinformationen, sowie eine Abfrage der Sprachauswahl (für 3 Sekunden) an und ist danach betriebsbereit.
MENU Nutzer-Profil 2 Info HW, SW... EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Telefon: 02162 / 3785-0 Telefax: 02162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.de Event P Event I UVD = { 0V...Unenn } Aktion = { KEINE | SIGNAL | WARNUNG |ALARM } Event U OPD = { 0W...Pnenn } Aktion = { KEINE | SIGNAL | WARNUNG |ALARM } OCD = {0A...Inenn } Aktion = { KEINE | SIGNAL | WARNUNG |ALARM } UCD = { 0A...Inenn } Aktion = { KEINE | SIGNAL | WARNUNG |ALARM } OVD = { 0V...
MENU EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Telefon: 02162 / 3785-0 Telefax: 02162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.de U(Offs) = U(A)…Umax-U(A) I nächste Seite DIN 40839 U(A)= 0V...Umax-U(Offs) U Trapez U(Start/End)=0V...Umax I(Limit)=0A...Imax P(Limit)=0W...Pmax Seq.Zyklen= Sequenz 4 Sequenz 5 U/I/P Limits DIN Zyklen Zeit t1= 0.01ms...36000s , 1...999 Seq.Zeit= 0.01ms...36000s Uend= 0V...Umax Sequenz 2 Sequenz 3 Ustart= 0V...
MENU Funkt. Generator Einst. 1 Us(AC)= 0V...Umax EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Telefon: 02162 / 3785-0 Telefax: 02162 / 16230 MPP-Tracking Batterietest XY-Tabelle Seite 1 Dynamisch Start: 1...100 U[1...100]: 0.00 V ... Unenn Wdh.: 0...65535 MPP4 Ende: 1...100 Isc: 0.0 A ... Inenn ∆t: 5 ms ... 65535 ms Pmpp: 0.0 W ... Pnenn Umpp: 0.00 V ... Unenn ∆P: 0.0 W ... 0,5 Pnenn MPP3 ∆t: 5 ms ... 65535 ms Uoc: 0.00 V ... Unenn ∆P: 0.0 W ... 0,5 Pnenn Isc: 0.0 A ...
MENU Kom.-Timeout HMI Einstellungen EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Telefon: 02162 / 3785-0 Telefax: 02162 / 16230 Ton ein Ton ein Tastenton Alarmton Limits Sperre Statusseite Alles sperren: HMI Sperre Helligkeit: Entsperren: Start Sperren: Alternative Statusseite: Meßleiste anzeigen: Ton aus Ton aus Benutzer-PIN ändern: Start PIN aktivieren: EIN/AUS zulassen: 60 Sekunden an: Hinterg.
EL 9000 B HP Serie 3.4.3.1 Menü „Allgemeine Einstellungen“ Einstellung Fernsteuerung erlauben S. Beschreibung 1 Bei Wahl „Nein“ kann das Gerät weder über eine der digitalen, noch über die analoge Schnittstelle fernbedient werden. Der Status, daß die Fernsteuerung gesperrt ist, wird im Statusfeld der Hauptanzeige mit „Lokal“ angezeigt. Siehe auch Abschnitt 1.9.5.1.
EL 9000 B HP Serie Einstellung Master-Slave-Modus S. Beschreibung 9 Mit Option „MASTER“ oder „SLAVE“ wird der Master-Slave-Modus (kurz: MS) aktiviert und gleichzeitig die Funktion des Gerätes im MS festgelegt. Näheres zum MS-Modus siehe Abschnitt „3.11.2. Parallelschaltung als Master-Slave (MS)“. PSI / ELR System 9 Master-Init.
EL 9000 B HP Serie IF Ebene 1 Ebene 2 IP Einstellungen DHCP Manuell Ebene 3 IP Gateway Ethernet / ModBus-TCP, 1 & 2 Port Subnet DNS 1 DNS 2 Port IP-Kom Einst. P1 AUTO IP-Kom Einst. P2 Manuell Half dup Full dup 10MBit 100MBit Host-Name Domäne TCP Keep-Alive TCP Keep-alive aktivieren Beschreibung Das IF läßt sich von einem DHCP-Server eine IP und ggf. eine Subnetzmaske, sowie Gateway zuweisen.
EL 9000 B HP Serie IF Ebene 1 Basis-ID Ebene 2 Ebene 3 Beschreibung Einstellung der CAN-Basis-ID (11 Bit oder 29 Bit, Hexadezimalformat). Standardwert: 0h Einstellung der CAN-Busgeschwindigkeit in den typischen Werten zwischen 10 kbps und 1Mbps. Standardwert: 500 kbps Terminierung Ein- oder Ausschalten des elektronisch geschalteten, im Modul befindlichen Busabschlußwiderstandes. Standardwert: AUS Broadcast ID Einstellung der CAN-Broadcast-ID (11 Bit oder 29 Bit, Hexadezimalformat).
EL 9000 B HP Serie Element Kom.-Timeout Beschreibung Timeout USB/RS232 (in Millisekunden) Standardwert: 5, Bereich: 5...65535 Stellt die Zeit ein, die max. bei zwischen der Übertragung von zwei Bytes oder Blöcken von Bytes ablaufen darf. Mehr dazu in der externen Dokumentation „Programming ModBus & SCPI“. Timeout ETH (in Sekunden) Standardwert: 5, Bereich: 5...65535 Stellt das bei Netzwerken bekannte „keep-alive timeout“ in Sekunden ein.
EL 9000 B HP Serie 3.4.4 Einstellgrenzen („Limits“) Die Einstellgrenzen gelten nur für die zugehörigen Sollwerte, jedoch gleichermaßen bei manueller Bedienung wie bei Fernsteuerung. Standardmäßig sind alle Sollwerte (U, I, P, R) von 0...100% einstellbar. Das kann in einigen Fällen, besonders zum Schutz von Anwendungen gegen Überstrom, hinderlich sein.
EL 9000 B HP Serie 3.4.6 Sollwerte manuell einstellen Die Einstellung der Sollwerte von Spannung, Strom, Leistung und Widerstand ist die grundlegende Bedienmöglichkeit der elektronischen Last und daher sind die beiden Drehknöpfe auf der Vorderseite des Gerätes bei manueller Bedienung stets zwei von den vier Sollwerten zugewiesen. Die Sollwerte können auf zwei Arten manuell vorgegeben werden: per Drehknopf oder Direkteingabe.
EL 9000 B HP Serie 3.4.7 Ansichtsmodus der Hauptanzeige wechseln Die Hauptanzeige, auch genannt Statusseite, mit ihren Soll- und Istwerten sowie den Gerätestatus, kann auf eine einfachere Darstellung umgeschaltet werden, die nur Werte von Spannung und Strom, sowie den Status anzeigt. Der Vorteil der alternativen Statusseite ist, daß die beiden Istwerte mit deutlich größeren Zahlen dargestellt werden, wodurch das Ablesen aus größerer Entfernung möglich wird.
EL 9000 B HP Serie 3.4.9 DC-Eingang ein- oder ausschalten Der DC-Eingang des Gerätes kann manuell oder ferngesteuert aus- oder eingeschaltet werden. Bei manueller Bedienung kann dies jedoch durch die Bedienfeldsperre verhindert sein. Das manuelle oder ferngesteuerte (digital) Einschalten des DC-Eingangs kann durch den Eingangspin REM-SB der eingebauten Analogschnittstelle gesperrt sein. Siehe dazu auch 3.4.3.1 und Beispiel a) in 3.5.4.7. In der Anzeige wird dann ein entsprechender Hinweis eingeblendet.
EL 9000 B HP Serie Legende: U set / I set / P set / R set: Sollwerte U actual / I actual / P actual / R actual: Istwerte Error: Gerätealarme Time: Zeit ab Start des Logging Device mode: aktuelle Regelungsart (siehe auch „3.2. Regelungsarten“) Hinweise: • R set und R actual werden nur aufgezeichnet, wenn der UIR-Modus aktiv ist (siehe dazu Abschnitt 3.4.
EL 9000 B HP Serie 3.5 Fernsteuerung 3.5.1 Allgemeines Fernsteuerung ist grundsätzlich über die eingebaute analoge oder die USB-Schnittstelle oder über eine der optional erhältlichen digitalen Schnittstellenmodule möglich. Wichtig ist dabei, daß entweder nur die analoge oder eine digitale im Eingriff sein kann.
EL 9000 B HP Serie 3.5.3.2 Allgemeines zu den Schnittstellenmodulen Bei allen Modellen der Serie EL 9000 B HP kann jeweils eins der in 3.5.3.1 genannten steck- und nachrüstbaren Module installiert sein. Über dieses kann das Gerät alternativ zu der fest eingebauten USB-Schnittstelle (Rückseite, Typ B) oder der fest eingebauten analogen Schnittstelle ferngesteuert werden. Zur Installation siehe „2.3.9. Installation eines Schnittstellenmoduls“ und separate Dokumentation.
EL 9000 B HP Serie 3.5.4.2 Quittieren von Alarmmeldungen Alarmmeldungen des Gerätes (siehe 3.6.2) erscheinen immer in der Anzeige, einige davon auch als Signal auf der analogen Schnittstelle (siehe Tabelle unten). Tritt während der Fernsteuerung über analoge Schnittstelle ein Gerätealarm auf, schaltet der DC-Eingang genauso aus wie bei manueller Bedienung. Bei den Alarmen Übertemperatur (OT), Power Fail (PF) und Überspannung (OV) kann das über die Signalpins der AS erfaßt werden, bei anderen Alarmen wie z.
EL 9000 B HP Serie 3.5.4.5 Übersicht Sub-D-Buchse 3.5.4.6 Prinzipschaltbilder der Pins 4.7k +10V 3.5.4.7 Analoger Eingang (AI) Digitaler Eingang (DI) + Es ist ein möglichst niederohmiger Schalter zu verwenden (Relaiskontakt, Schalter, Schütz o.ä.), um das Signal sauber nach DGND zu schalten. 12V V~0.5 AGND Analoger Ausgang (AO) Digitaler Ausgang (DO) Ein Quasi-Open-Collector, weil hochohmiger Pullup-Widerstand gegen interne Versorgung.
EL 9000 B HP Serie • Fernsteuerung wurde nicht aktiviert In diesem Modus stellt der Pin eine Art Freigabe der Taste „On/Off“ am Bedienfeld des Gerätes bzw. des Befehls „DC-Eingang ein/aus“ (bei digitaler Fernsteuerung) dar. Daraus ergeben sich folgende mögliche Situationen: DCEingang + Pin „REM-SB“ + HIGH + HIGH ist aus LOW LOW + + + + + Parameter Verhalten „REM-SB“ DC-Eingang nicht gesperrt. Er kann mit Taste On/Off oder Befehl normal (dig. Fernsteuerung) eingeschaltet werden.
EL 9000 B HP Serie 3.6 Alarme und Überwachung 3.6.1 Begriffsdefinition Grundsätzlich wird unterschieden zwischen Gerätealarmen (siehe „3.3. Alarmzustände“) wie Überspannung und benutzerdefinierten Ereignissen, wie z. B. OCD (Überstromüberwachung).
EL 9000 B HP Serie Manche Gerätealarme können konfiguriert werden: Alarm Bedeutung Beschreibung Einstellbereich Meldeorte OVP Überspannungsschutz. Löst einen Alarm aus, wenn die OverVoltage Eingangsspannung am DC-Eingang die eingestellte 0 V...1,03*UNenn Protection Schwelle erreicht. Außerdem wird der DC-Eingang ausgeschaltet. Anzeige, Analogschnittst., digitale Schnittstellen OCP Überstromschutz. Löst einen Alarm aus, wenn der OverCurrent Eingangsstrom am DC-Eingang die eingestellte 0 A...
EL 9000 B HP Serie 3.6.2.1 Benutzerdefinierbare Ereignisse (Events) Die Überwachungsfunktion des Gerätes kann über benutzerdefinierbare Ereignisse, nachfolgend Events genannt, konfiguriert werden. Standardmäßig sind die Events deaktiviert (Aktion: KEINE) und funktionieren im Gegensatz zu Gerätealarmen nur solange der DC-Eingang eingeschaltet ist. Das bedeutet, zum Beispiel, daß keine Unterspannung mehr erfaßt würde, nachdem der Eingang ausgeschaltet wurde und die Spannung noch fällt.
EL 9000 B HP Serie 3.7 Bedieneinheit (HMI) sperren Um bei manueller Bedienung die versehentliche Verstellung eines Wertes zu verhindern, können die Drehknöpfe sowie der Touchscreen gesperrt werden, so daß keine Verstellung eines Wertes per Drehknopf oder Bedienung per Touchscreen angenommen wird, ohne die Sperre vorher wieder aufzuheben. ►►So sperren Sie das HMI 1. Tippen Sie auf der Hauptseite oben rechts auf das Schloßsymbol . 2.
EL 9000 B HP Serie 3.9 Nutzerprofile laden und speichern Das Menü „Profile“ dient zur Auswahl eines Profils zum Laden bzw. zum Wechsel zwischen einem Standardprofil und 5 Nutzerprofilen. Ein Profil ist eine Sammlung aller Einstellungen und aller Sollwerte. Bei Auslieferung des Gerätes bzw. nach einem Zurücksetzungsvorgang haben alle sechs Profile dieselben Einstellungen und sämtliche Sollwerte sind auf 0.
EL 9000 B HP Serie 3.10 Der Funktionsgenerator 3.10.1 Einleitung Der eingebaute Funktionsgenerator (kurz: FG) ist in der Lage, verschiedenförmige Signalformen zu erzeugen und diese auf einen der Sollwerte Spannung (U) oder Strom (I) anzuwenden. Die Standard-Funktionen basieren auf einem variablen Arbiträrgenerator. Bei manueller Bedienung können die Funktionen einzeln ausgewählt, konfiguriert und bedient werden.
EL 9000 B HP Serie 3.10.4 Manuelle Bedienung 3.10.4.1 Auswahl und Steuerung einer Funktion Über den Touchscreen kann eine der in 3.10.1 genannten Funktionen aufgerufen werden, konfiguriert und gesteuert werden. Auswahl und Konfiguration sind nur bei ausgeschaltetem Eingang möglich. ►►So wählen Sie eine Funktion aus und stellen Parameter ein 1. Tippen Sie bei ausgeschaltetem DC-Eingang auf das Bedienfeld . 2. Im Menü tippen Sie auf und danach auf die gewünschte Funktion. 3.
EL 9000 B HP Serie ►►So starten und stoppen Sie eine Funktion 1. Sie können die Funktion starten, indem Sie entweder auf das Bedienfeld tippen oder die Taste „On/Off“ betätigen, sofern der Eingang momentan aus ist. Die Funktion startet dann sofort. Sollte der DCEingang bei Betätigung von START ausgeschaltet sein, wird er automatisch eingeschaltet. 2.
EL 9000 B HP Serie Bildliche Darstellung: Anwendung und Resultat: Es wird ein dreieckförmiges Signal für den Eingangsstrom (direkt) oder die Eingangsspannung (indirekt) erzeugt. Die Zeiten der ansteigenden und abfallenden Flanken sind variabel und unterschiedlich einstellbar. A Der Offset verschiebt das Signal auf der Y-Achse. Amplitude Die Summe der Zeiten t1 und t2 ergibt die Periodendauer und deren Kehrwert eine Frequenz.
EL 9000 B HP Serie 3.10.8 Trapez-Funktion Folgende Parameter können für die Trapez-Funktion konfiguriert werden: Wert Einstellbereich Erläuterung I(A), U(A) 0...(Nennwert - (Offs)) von U, I A = Amplitude des zu generierenden Signals I(Offs), U(Offs) 0...(Nennwert - (A)) von U, I Offs = Offset, bezogen auf den Fußpunkt des Trapezes t1 0,01 ms...36000 s Zeit der ansteigenden Flanke des Trapezsignals t2 0,01 ms...36000 s Zeit des High-Wertes (Haltezeit) des Trapezsignals t3 0,01 ms...
EL 9000 B HP Serie 3.10.10 Arbiträr-Funktion Die Arbiträr-Funktion (arbiträr = beliebig) bietet dem Anwender einen erweiterten Spielraum. Es sind je 100 Sequenzen für die Zuordnung zum Strom I und der Spannung U verfügbar, die alle mit den gleichen Parametern versehen, aber durch die Werte unterschiedlich konfiguriert werden können, um so komplexe Funktionsabläufe „zusammenzubauen“. Von den 100 verfügbaren Sequenzen können 1...100 nacheinander ablaufen. Das ergibt einen Sequenzblock.
EL 9000 B HP Serie Bildliche Darstellungen: Anwendungen und Resultate: A Betrachtung 1 Ablaufs 1 Sequenz aus 100: Start (DC) Ende (DC) St ar t( En d e AC ) (A C ) Beispiel 2 t Seq.Zeit Die DC-Werte von Start und Ende sind gleich, die AC-Werte (Amplitude) jedoch nicht. Der Endwert ist größer als der Startwert, daher wird die Amplitude mit jeder neu angefangenen Sinushalbwelle kontinuierlich zwischen Anfang und Ende der Sequenz größer.
EL 9000 B HP Serie Durch Aneinanderreihung mehrerer unterschiedlich konfigurierter Sequenzen können komplexe Abläufe erzeugt werden. Dabei kann durch geschickte Konfiguration der Arbiträrgenerator die anderen Funktionen wie Dreieck, Sinus, Rechteck oder Trapez nachbilden und somit z. B. eine Sequenz aus Rechteck-Funktionen mit unterschiedlichen Amplituden bzw. Duty Cycles erzeugen.
EL 9000 B HP Serie 3.10.10.1 Laden und Speichern von Arbiträr-Funktionen Die manuell am Gerät konfigurierbaren 100 Sequenzen der Arbiträrfunktion, die auf Spannung U oder Strom I anwendbar ist, können über die USB-Schnittstelle auf der Vorderseite des Gerätes auf einen USB-Stick (nur FAT32-formatiert) gespeichert oder von diesem geladen werden. Dabei gilt, daß beim Speichern immer alle 100 Sequenzen in eine Textdatei vom Typ CSV gespeichert werden, beim Laden umgekehrt genauso.
EL 9000 B HP Serie ►►So speichern Sie die 100 Sequenzen vom Gerät auf einen USB-Stick 1. Stecken Sie den USB-Stick noch nicht ein bzw. ziehen Sie ihn zunächst heraus. 2. Öffnen Sie das Funktionsauswahlmenü des Funktionsgenerators über MENU -> Funkt.Generator -> Arbiträr -> U/I 3. Tippen Sie auf , dann . Sie werden aufgefordert, den USB-Stick einzustecken. Das Gerät sucht daraufhin nach dem Ordner HMI_FILES auf dem Speicherstick und nach eventuell schon vorhandenen WAVE_U- bzw.
EL 9000 B HP Serie Man könnte somit das Verhalten der Last bzw. die Strom- und Leistungsaufnahme in Abhängigkeit von der Eingangsspannung steuern und Lastsprünge erzeugen. Beim Laden einer Tabelle vom USB-Stick werden nur Textdateien vom Typ CSV akzeptiert. Die Tabelle wird beim Laden auf Plausibilität überprüft (Werte nicht zu groß, Anzahl der Werte korrekt) und eventuelle Fehler gemeldet und dann die Tabelle nicht geladen.
EL 9000 B HP Serie 3.10.13 Batterietest-Funktion Die Batterietest-Funktion dient zum gezielten Entladen von Batterien unterschiedlicher Art in industriellen Produkttests oder auch in Laboranwendungen. Diese Funktion ist so wie unten beschrieben nur über manuelle Bedienung am HMI verfügbar, kann aber wie die anderen Funktionen über den Arbiträrgenerator in Fernsteuerung nachgebildet werden.
EL 9000 B HP Serie 3.10.13.3 Globale Parameter Parameter Einstellbereich Erläuterung Entlade-Spannung 0...Nennwert von U Variable Entladeschlußspannung, eine Schwelle, bei deren Unterschreiten der Test automatisch stoppt (ist verknüpft mit der Batteriespannung am DC-Eingang der Last) Entladezeit 0...10 h Maximale Testzeit, nach welcher der Test automatisch stoppt Entlade-Kapazität 0...
EL 9000 B HP Serie 3.10.13.6 Abbruchbedingungen Der Ablauf der Batterietest-Funktion kann gewollt oder ungewollt durch stoppen bzw. gestoppt werden durch: • • • • • Manuelle Betätigung des Bedienfeldes STOP in der Anzeige Irgendeinen Geräte-Alarm wie OT usw. Erreichen der eingestellten max. Testzeit, wenn dafür Aktion = Test-Ende eingestellt ist Erreichen des eingestellten max.
EL 9000 B HP Serie 3.10.14.2 Modus MPP2 Dieser Modus simuliert das eigentliche Trackingverhalten eines Solarwechselrichters, indem der Funktionsablauf nach dem Finden des MPP nicht gestoppt, sondern um den MPP herum geregelt wird. Das geschieht, der Natur eines Solarpaneels geschuldet, immer unterhalb des MPP. Nach Erreichen des MPP sinkt die Spannung zunächst und somit auch die Leistung.
EL 9000 B HP Serie 3.10.15 Fernsteuerung des Funktionsgenerators Der Funktionsgenerator ist fernsteuerbar, allerdings geschehen die Konfiguration und Steuern von Funktionen mittels einzelner Befehle und prinzipiell anders als bei manueller Bedienung. Die externe Dokumentation „Programmieranleitung ModBus & SCPI“ erläutert die Vorgehensweise.
EL 9000 B HP Serie 3.11 Weitere Anwendungen 3.11.1 Reihenschaltung Reihenschaltung ist keine zulässige Betriebsart von elektronischen Lasten und darf daher unter keinen Umständen so verbunden und betrieben werden! 3.11.2 Parallelschaltung als Master-Slave (MS) Mehrere Geräte gleicher Art und gleichen Modells können zu einer Parallelschaltung verbunden werden, um eine höhere Gesamtleistung zu erzielen.
EL 9000 B HP Serie ►►So stellen Sie die Master-Slave-Verbindung her 1. Alle zu verbindenden Geräte ausschalten und mittels Netzwerkkabel (CAT3 oder besser, nicht im Lieferum2. fang des Gerätes enthalten) untereinander verbinden. Dabei ist es egal, welche der beiden Master-SlaveAnschlußbuchsen (RJ45, Rückseite) zum jeweils nächsten Gerät verbunden wird. Je nach gewünschter Konfiguration nun auch die Geräte DC-seitig verbinden.
EL 9000 B HP Serie 3.11.2.5 Bedienung des Master-Slave-Systems Nach erfolgreicher Konfiguration und Initialisierung des Master-Gerätes und der Slave-Geräte zeigen diese ihren Status in der Anzeige an. Der Master zeigt lediglich „Master“ im Statusfeld, die Slaves zeigen, solange wie durch den Master ferngesteuert, den Status wie rechts im Bild an: Die Slaves sind dann nicht manuell bedienbar und auch nicht per analoger oder digitaler Schnittstelle fernsteuerbar.
EL 9000 B HP Serie • Falls das Master-Gerät AC-seitig ausfällt (ausgeschaltet am Netzschalter, Stromausfall) und später wiederkommt, initialisiert es automatisch das MS-System neu und bindet alle erkannten Slaves ein. In diesem Fall kann MSBetrieb automatisch fortgeführt werden, wenn z. B. eine Software das Master-Gerät überwacht und steuert. • Falls mehrere Master-Geräte oder gar keines definiert wurde, kann das Master-Slave-System nicht initialisiert werden.
EL 9000 B HP Serie 3.11.3 Zwei-Quadranten-Betrieb (2QB) 3.11.3.1 Einleitung Diese Betriebsart bezieht sich auf die Verwendung einer Quelle, in dem Fall ein Netzgerät aus einer kompatiblen Serie (siehe „1.9.9. Share-Bus-Anschluß“)und einer Senke, hier eine elektronische Last der Serie EL 9000 B HP. Die Quelle und die Senke treten abwechselnd in Funktion, um einen Prüfling, wie z. B. eine Batterie, im Rahmen eines Funktions- oder Endtests gezielt zu laden und zu entladen.
EL 9000 B HP Serie 3.11.3.3 Einstellungen an den Geräten Die Master-Slave-Einstellungen im MENU wirken sich auch auf die Funktion des Share-Bus‘ aus. Für den korrekten Betrieb des 2QB muß an den beteiligten Lasten sichergestellt sein, daß sie auf den Share-Bus nicht bestimmend einwirken. Das geschieht bei Slave-Lasten automatisch mit der Master-Slave-Einstellung SLAVE bzw. wenn kein Master-Slave-Betrieb gefahren wird, mit Einstellung OFF.
EL 9000 B HP Serie 4. Instandhaltung & Wartung 4.1 Wartung / Reinigung Die Gerät erfordern keine Wartung. Reinigung kann, jenachdem in welcher Umgebung sie betrieben werden, früher oder später für die internen Lüfter nötig sein. Diese dienen zur Kühlung der internen Komponenten, die durch die zwangsweise entstehende, hohe Verlustleistung erhitzt werden. Stark verdreckte Lüfter können zu unzureichender Luftzufuhr führen und damit zu vorzeitiger Abschaltung des DC-Eingangs wegen Überhitzung bzw.
EL 9000 B HP Serie 4.3 Nachjustierung (Kalibrierung) 4.3.1 Einleitung Die Geräte der Serie EL 9000 B HP verfügen über eine Nachjustierungsfunktion, die im Rahmen einer Kalibrierung dazu dient, Abweichungen zwischen den Stellwerten und tatsächlichen Werten bis zu einem gewissen Grad zu kompensieren. Gründe, die eine Nachjustierung der Gerätestellwerte nötig machen, gibt es einige: Bauteilalterung, Bauteilverschleiß, extreme Umgebungsbedingungen, häufige Benutzung.
EL 9000 B HP Serie 4.3.3.1 Sollwerte ►►So gleichen Sie die Spannung ab 1. Die Spannungsquelle auf etwa 102% Nennspannung des EL-Gerätes, in 2. diesem Beispiel dann rechnerisch 81,6 V, einstellen und deren Ausgang einschalten. Die Strombegrenzung der Quelle auf 5% des Nennstromes der Last, hier 8,5 A, einstellen. Prüfen Sie zu nochmals, daß für den Spannungsabgleich der Fernfühlungseingang (Sense) hinten am Gerät nicht verbunden ist. In der Anzeige der EL in das MENU wechseln, dann „Allg.
EL 9000 B HP Serie 4.3.3.3 Speichern und beenden Zum Schluß kann noch über das Bedienfeld gegeben und auch abgerufen werden. das Datum des Abgleichs im Format JJJJ / MM / TT ein- Danach sollten die Abgleichwerte unbedingt noch mit dem Bedienfeld gespeichert werden. Verlassen des Abgleichmenüs ohne auf „Speichern und beenden“ zu tippen verwirft alle ermittelten Abgleichdaten und die Abgleichprozedur müßte wiederholt werden! 5. Service & Support 5.
EA-Elektro-Automatik GmbH & Co. KG Entwicklung - Produktion - Vertrieb Helmholtzstraße 31-37 41747 Viersen Telefon: 02162 / 37 85-0 Telefax: 02162 / 16 230 ea1974@elektroautomatik.de www.elektroautomatik.
Elektro-Automatik Operating Manual EL 9000 B HP Electronic DC Load Doc ID: EL9HEN Revision: 01 Date: 04/2017
EL 9000 B HP Series TABLE OF CONTENTS 1 GENERAL 1.1 1.1.1 1.1.2 1.1.3 1.1.4 1.2 1.3 1.4 1.5 1.6 1.7 1.7.1 1.7.2 1.7.3 1.7.4 1.7.5 1.8 1.8.1 1.8.2 1.8.3 1.8.4 1.8.5 1.9 1.9.1 1.9.2 1.9.3 1.9.4 1.9.5 1.9.6 1.9.7 1.9.8 1.9.9 1.9.10 1.9.11 2 About this document.......................................5 Retention and use...........................................5 Copyright.........................................................5 Validity.............................................................
EL 9000 B HP Series 3.10.7 3.10.8 3.10.9 3.10.10 3.10.11 3.10.12 3.10.13 3.10.14 3.10.15 3.11 3.11.1 3.11.2 3.11.3 Rectangular function.....................................62 Trapezoidal function......................................63 DIN 40839 function.......................................63 Arbitrary function...........................................64 Ramp function...............................................68 UI and IU table functions (XY table).............68 Battery test function...............
EL 9000 B HP Series 1. General 1.1 About this document 1.1.1 Retention and use This document is to be kept in the vicinity of the equipment for future reference and explanation of the operation of the device. This document is to be delivered and kept with the equipment in case of change of location and/or user. 1.1.2 Copyright Reprinting, copying, also partially, usage for other purposes as foreseen of this manual are forbidden and breach may lead to legal process. 1.1.
EL 9000 B HP Series 1.4 Disposal of equipment A piece of equipment which is intended for disposal must, according to European laws and regulations (ElektroG, WEEE) be returned to EA Elektro-Automatik for scrapping, unless the person operating the piece of equipment or another, delegated person is conducting the disposal. Our equipment falls under these regulations and is accordingly marked with the following symbol: 1.
EL 9000 B HP Series 1.7 Safety 1.7.1 Safety notices Mortal danger - Hazardous voltage • Electrical equipment operation means that some parts will be under dangerous voltage. Therefore all parts under voltage must be covered! • All work on connections must be carried out under zero voltage (input not connected to voltage sources) and may only be performed by qualified and informed persons. Improper actions can cause fatal injury as well as serious material damage.
EL 9000 B HP Series 1.7.3 Responsibility of the operator Operator is any natural or legal person who uses the equipment or delegates the usage to a third party, and is responsible during its usage for the safety of the user, other personnel or third parties. The equipment is in industrial operation. Therefore the operators are governed by the legal safety regulations.
EL 9000 B HP Series 1.7.5 Alarm signals The equipment offers various possibilities for signalling alarm conditions, however, not for danger situations. The signals may be optical (on the display as text) acoustic (piezo buzzer) or electronic (pin/status output of an analog interface). All alarms will cause the device to switch off the DC input.
EL 9000 B HP Series 1.8.3 Specific technical data Up to 1200 W Model HP EL 9080-85 B EL 9200-35 B EL 9360-20 B EL 9500-15 B EL 9750-10 B Supply voltage 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC Connection type Wall socket Wall socket Wall socket Wall socket Wall socket Frequency 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz Fuse T 6.3 A T 6.3 A T 6.3 A T 6.3 A T 6.3 A Power consumption max. 45 W max. 45 W max. 45 W max. 45 W max.
EL 9000 B HP Series Up to 1200 W Analog interface Model HP EL 9080-85 B EL 9200-35 B EL 9360-20 B EL 9500-15 B EL 9750-10 B (1 Set value inputs U, I, P, R Actual value output U, I Control signals DC on/off, Remote on/off, R mode on/off Status signals CV, OVP, OT Galvanic isolation to the device max. 1500 V DC Sample rate (set value inputs) 500 Hz Insulation Input (DC) to enclosure Input (AC) to input (DC) DC minus: permanent max. ±400 V DC plus: permanent max. ±400 V + max.
EL 9000 B HP Series Up to 2400 W Model HP EL 9080-170 B EL 9200-70 B EL 9360-40 B EL 9500-30 B EL 9750-20 B Supply voltage 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC 90...264 V AC Connection type Wall socket Wall socket Wall socket Wall socket Wall socket Frequency 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz 45...65 Hz Fuse T 6.3 A T 6.3 A T 6.3 A T 6.3 A T 6.3 A Power consumption max. 45 W max. 45 W max. 45 W max. 45 W max. 45 W Leak current < 3.5 mA < 3.
EL 9000 B HP Series Up to 2400 W Analog interface Model HP EL 9080-170 B EL 9200-70 B EL 9360-40 B EL 9500-30 B EL 9750-20 B (1 Set value inputs U, I, P, R Actual value output U, I Control signals DC on/off, Remote on/off, R mode on/off Status signals CV, OVP, OT Galvanic isolation to the device max. 1500 V DC Sample rate (set value inputs) 500 Hz Insulation Input (DC) to enclosure Input (AC) to input (DC) DC minus: permanent max. ±400 V DC plus: permanent max. ±400 V + max.
EL 9000 B HP Series Views A - Power switch B - Control panel C - Control interfaces (digital, analog) D - Share Bus and remote sensing connection E - DC input (screw terminal for M6 screws) F - AC socket G - Master-Slave ports 1.8.4 Figure 1 - Front view EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Figure 2 - Rear view Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.
EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 Figure 4 - Right hand side, without DC cover Figure 3 - Left hand side, with DC cover EL 9000 B HP Series www.elektroautomatik.de ea1974@elektroautomatik.
EL 9000 B HP Series Figure 5 - Top view EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.
EL 9000 B HP Series 1.8.5 Control elements Figure 6 - Control Panel Overview of the elements of the operating panel For a detailed description see section „1.9.5. The control panel (HMI)“.
EL 9000 B HP Series 1.9 Construction and function 1.9.1 General description The HP in the series name EL 9000 B HP stands for “high power”and points to an improved characteristics regarding the thermal derating which is typical for conventional loads. For this series, the rated steady power is defined up to 30 °C ambient temperature, compared to the EL 9000 B series where it is defined up to 25 °C (.
EL 9000 B HP Series 1.9.3 Scope of delivery 1 x Electronic load device 1 x Share Bus plug 1 x Remote sensing plug 2 x Fill strip (for the purpose see 2.3.3.1) 1 x 1.8 m USB cable 1 x Set of DC terminal cover(s) 1 x USB stick with documentation and software 1 x Mains cord (IEC, schuko, 10 A) 1 x UK wall socket adapter (only included in delivery to the UK) 1.9.4 Accessories For these devices the following accessories are available: Digital interface modules IF-AB EA Elektro-Automatik GmbH Helmholtzstr.
EL 9000 B HP Series 1.9.5 The control panel (HMI) The HMI (Human Machine Interface) consists of a display with touchscreen, two rotary knobs, a button and an USB-A port. 1.9.5.1 Touchscreen display The graphic touchscreen display is divided into a number of areas. The complete display is touch sensitive and can be operated by finger or stylus to control the equipment.
EL 9000 B HP Series • Status display (upper right) This area displays various status texts and symbols: Display Description Locked The HMI is locked Unlocked The HMI is unlocked Remote: The device is under remote control from.... Analog ....the built-in analog interface USB & others ....the built-in USB port or a plug in interface module Local The device has been locked by the user explicitly against remote control Alarm: Alarm condition which has not been acknowledged or still exists.
EL 9000 B HP Series 1.9.5.4 Resolution of the displayed values In the display, set values can be adjusted in fixed increments. The number of decimal places depends on the device model. The values have 4 or 5 digits. Actual and set values always have the same number of digits. Adjustment resolution and number of digits of set values in the display: 80 V 200 V 360 V 500 V 750 V 0.01 V 0.01 V 0.1 V 0.1 V 0.1 V 10 A - 20 A 30 A - 85 A 170 A Increment 5 0.001 A 4 0.01 A 5 0.
EL 9000 B HP Series 1.9.6 USB-Port Type B (Back side) The USB-B port on the back side of the device is provided for communication with the device and for firmware updates. The included USB cable can be used to connect the device to a PC (USB 2.0 or 3.0). The driver is delivered on the included medium (USB stick) and installs a virtual COM port. The device can be addressed via this port either using the international standard ModBus protocol or by SCPI language.
EL 9000 B HP Series 1.9.9 “Share” connector The 2 pole socket (“Share”) on the back side of the device is provided for connection to equally named sockets on compatible electronic loads when establishing parallel connection where symmetric current distribution is required, as well as compatible power supplies to build a two-quadrants operation setup. For details about this feature refer to „3.11.2. Parallel operation in master-slave (MS)“ and „3.11.3. Two quadrants operation (2QO)“.
EL 9000 B HP Series 2. Installation & commissioning 2.1 Transport and storage 2.1.1 Transport • The handles on the front side of the device are not for carrying! • Because of its weight, transport by hand should be avoided where possible. If unavoidable then only the housing should be held and not on the exterior parts (handles, DC input terminal, rotary knobs).
EL 9000 B HP Series 2.3.2 Preparation Connection to mains of electronic loads of EL 9000 B HP only requires a standard wall socket. The mains cord is included in the scope of delivery. The devices only consume little power, so there are no further installation or safety measures required. The loads can also be operated together with different devices on the same distribution box. 2.3.
EL 9000 B HP Series 2.3.4 Connection to DC sources In the case of a device with a high nominal current and hence a thick and heavy DC connection cable it is necessary to take account of the weight of the cable and the strain imposed on the DC connection. Especially when mounted in a 19” cabinet or similar, where the cable hangs on the DC input, a strain reliever has to be used. The DC input is on the back side of the device and is not protected by a fuse.
EL 9000 B HP Series 2.3.5 Grounding of the DC input The device can always be grounded on the DC minus pole, i.e. can be directly connected to PE. The DC plus pole, however, if it is to be grounded, may only be so for input voltages up to 400 V, because the potential of the minus pole is shifted into negative direction by the value of the input voltage. Also see technical specification sheets in 1.8.3, item “Insulation”.
EL 9000 B HP Series and switch the device on. 2.3.8.1 Driver installation (Windows) On the initial connection with a PC the operating system will identify the device as new hardware and will try to install a driver. The required driver is for a Communications Device Class (CDC) device and is usually integrated in current operating systems such as Windows 7 or 10.
EL 9000 B HP Series 2.3.10 Connecting the analog interface The 15 pole connector (Type: Sub-D, D-Sub) on the rear side is an analog interface. To connect this to a controlling hardware (PC, electronic circuit), a standard plug is necessary (not included in the scope of delivery). It is generally advisable to switch the device completely off before connecting or disconnecting this connector, but at least the DC input. The analog interface is galvanically isolated from the device internally.
EL 9000 B HP Series 3. Operation and application 3.
EL 9000 B HP Series 3.2.2 Current regulation / constant current / current limitation Current regulation is also known as current limitation or constant current mode (CC) and is fundamental to the normal operation of an electronic load. The DC input current is held at a predetermined level by varying the internal resistance according to Ohm’s law R = U / I such that, based on the input voltage, a constant current flows.
EL 9000 B HP Series Principle view of the derating characteristics: Starting at around 30°C (86°F) ambient temperature, the derating will continuously step down the available input power. P The temperature range of the device is rated up to 50°C (122°F). Above that point, the system could shut down because of overtemperature (OT). However, due to the continuous derating that will happen, if at all, only above 80°C (176°F). 10°C 3.2.
EL 9000 B HP Series 3.3 Alarm conditions This section only gives an overview about device alarms. What to do in case your device indicates an alarm condition is described in section „3.6 Alarms and monitoring“ on page 54. As a basic principle, all alarm conditions are signalled optically (text + message in the display), acoustically (if activated) and as a readable status and alarm counter via the digital interface. In addition, the alarms OT and OVP are reported as signals on the analogue interface.
EL 9000 B HP Series 3.4 Manual operation 3.4.1 Powering the device The device should, as far as possible, always be switched on using the toggle switch on the front of the device. Alternatively this can take place using an external cutout (contactor, circuit breaker) of suitable current capacity. After switching on, the display firsts show the manufacturers logo and device related information, as well as a language selection screen (for 3 s) and will then be ready for use. In setup (see section „3.4.3.
MENU User Profile 2 About HW, SW... EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.de Event P Event I UVD = {0V...Unom} Action = {NO | SIGNAL | WARNING |ALARM} Event U OPD = {0W...Pnom} Action = {NO | SIGNAL | WARNING |ALARM} OCD = {0A...Inom} Action = {NO | SIGNAL | WARNING |ALARM} UCD = {0A...Inom} Action = {NO | SIGNAL | WARNING |ALARM} OVD = {0V...
MENU EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 www.elektroautomatik.de ea1974@elektroautomatik.de U(Offs) = U(A)…Umax-U(A) I next page DIN 40839 U(A)= 0V...Umax-U(Offs) U Trapezoid P(Limit)=0W...Pmax Seq.cycles= U/I/P Limits DIN Repetition Time t1= 0.01ms...36000s , 1...999 I(Limit)=0A...Imax Sequence 5 Seq.time= 0.01ms...36000s Sequence 3 U(Start/End)=0V...Umax Uend= 0V...Umax Sequence 2 Sequence 4 Ustart= 0V...
MENU Function Generator Settings 1 Us(AC)= 0V...Umax EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 MPP Tracking Battery test XY Table Isc: 0.0 A ... Inom ∆t: 5 ms ... 65535 ms Pmpp: 0.0 W ... Pnom Start: 1...100 Umpp: 0.00 V ... Unom ∆P: 0.0 W ... 0.5 Pnom U[1...100]: 0.00 V ... Unom Rep.: 0...65535 MPP3 MPP4 End: 1...100 ∆t: 5 ms ... 65535 ms Isc: 0.0 A ... Inom Uoc: 0.00 V ... Unom ∆P: 0.0 W ... 0.5 Pnom MPP2 ∆t: 5 ms ...
MENU Com Timeout HMI Setup EA Elektro-Automatik GmbH Helmholtzstr. 31-37 • 41747 Viersen Germany Sound on Alarm Sound Fon: +49 2162 / 3785-0 Fax: +49 2162 / 16230 Limits Lock Status page Sound on Lock all: Key Sound HMI Lock Brightness: Unlock: Start Lock: Alternative status page: Show meter bar: Sound off Sound off Change user PIN: Start Enable PIN: ON/OFF possible: Off after 60 sec: Backlight Always on: English, Deutsch, Русский, 中文 ModBus: SCPI: Timeout ETH (s): 5...
EL 9000 B HP Series 3.4.3.1 Menu “General Settings” Setting Allow remote control P. Description 1 Selection “NO” means that the device cannot be remotely controlled over either the digital or analog interfaces. If remote control is not allowed, the status will be shown as “Local” in the status area on the main display. Also see section 1.9.5.1. Analog interface range 1 Selects the voltage range for the analog set input values, monitoring outputs and reference voltage output. • 0...5 V = Range is 0...
EL 9000 B HP Series Setting PSI / ELR system P. Description 9 This item will only be displayed if the device is set as MASTER When activated by finger touch (check mark), it determines that the electronic load is part of a two-quadrant operation (2QO, see „3.11.3. Two quadrants operation (2QO)“) system and thus it will be slave on the Share bus, which is required for a 2QO, because in 2QO all load units have to be slaves. Repeat master init.
EL 9000 B HP Series Ethernet / ModBus-TCP, 1 & 2 Port IF Level 1 IP Settings Level 2 DHCP Level 3 Description The IF allows a DHCP server to allocate an IP address, a subnet mask and a gateway. If no DHCP server is in the network then network parameters will be set as defined in item “Manual” Manual IP This option is activated by default. An IP address can be manually allocated. Gateway Here a gateway address can be allocated if required..
EL 9000 B HP Series IF Ebene 1 Base ID Level 2 Level 3 Description Setup of the CAN base ID (11 Bit or 29 Bit, hex format). Default: 0h Setup of the CAN bus speed or baud rate in typical value between 10 kbps and 1Mbps. Default: 500 kbps Termination Activates or deactivates CAN bus termination with a built-in resistor. Default: OFF Broadcast ID Setup of the CAN broadcast ID (11 Bit or 29 Bit, hex format). Default: 7ffh ID Format Selection of the CAN ID format between Base (11 Bit ID, 0h...
EL 9000 B HP Series Element Com Timeout Description Timeout USB/RS232 (in milliseconds) Default value: 5, Range: 5...65535 Defines the max. time between two subsequent bytes or blocks of a transferred message. For more information about the timeout refer to the external programming documentation “Programming ModBus & SCPI”. Timeout ETH (in seconds) Default value: 5, Range: 5...65535 Defines the “keep-alive timeout” property of a network connection in seconds.
EL 9000 B HP Series 3.4.4 Adjustment limits Adjustment limits are only effective on the related set values, no matter if using manual adjustment or remote control! Defaults are, that all set values (U, I, P, R) are adjustable from 0 to 100%. This may be obstructive in some cases, especially for protection of applications against overcurrent. Therefore upper and lower limits for current (I) and voltage (U) can be set which limit the range of the adjustable set values.
EL 9000 B HP Series 3.4.6 Manual adjustment of set values The set values for voltage, current, power and resistance are the fundamental operating possibilities of an electronic load and hence the two rotary knobs on the front of the device are always assigned to two of the four values in manual operation. The set values can be entered manually in two ways: via rotary knob or direct input. Entering a value changes it immediately, no matter if the DC input is switched on or off.
EL 9000 B HP Series Limitations of the alternative status page: • Set and actual values of power are not displayed and the set value of power is only indirectly accessible • Set value of resistance is not displayed and only indirectly accessible • No access to the settings overview (MENU button) while the DC input is on In alternative status page mode, the set values of power and resistance are not adjustable while the DC input is switched on.
EL 9000 B HP Series 3.4.10 Recording to USB stick (logging) Device data can be recorded to USB stick (2.0 / 3.0 may work, but not all vendors are supported) anytime. For specifications of the USB stick and the generated log files refer to section „1.9.5.5. USB-Port (Front side)“. The logging stores files of CSV format on the stick. The layout of the log data is the same as when logging via PC with software EA Power Control.
EL 9000 B HP Series 3.5 Remote control 3.5.1 General Remote control is possible via the built-in analog or USB port or via one of the optional interface modules. Important here is that only the analog or one digital interface can be in control. It means that if, for example, an attempt were to be made to switch to remote control via the digital interface whilst analog remote control is active, the device would report an error via the digital interface.
EL 9000 B HP Series 3.5.3.2 General information about the interface modules With all models of series EL 9000 B HP, one of the plug-in and retrofittable modules listed in 3.5.3.1 can be installed. It can take over remote control of the device alternatively to the built-in USB type B on the back side or the analog interface. For installation see section „2.3.9. Installation of an interface module“ and separate documentation.
EL 9000 B HP Series 3.5.4.2 Acknowledging device alarms Device alarms (see 3.6.2) are always indicated in the front display and some of them are also reported as signal on the analog interface socket (see table below). In case of a device alarm occurring during remote control via analog interface, the DC input will be switched off the same way as in manual control.
EL 9000 B HP Series 3.5.4.5 Overview of the Sub-D Socket 3.5.4.6 Simplified diagram of the pins Digital Input (DI) + Analog Input (AI) It requires to use a switch with low resistance (relay, switch, circuit breaker etc.) in order to send a clean signal to the DGND. V~0.5 High resistance input (impedance >40 k....100 kΩ) for an OA circuit. AGND 4.7k +10V 3.5.4.7 12V Digital Output (DO) Analog Output (AO) A quasi open collector, realised as high resistance pull-up against the internal supply.
EL 9000 B HP Series • Remote control is not active In this mode of operation pin “REM-SB” can serve as lock, preventing the DC input from being switched on by any means. This results in following possible situations: DCinput + Pin „REM-SB“ + HIGH is off + LOW HIGH LOW + + + + + Parameter Behaviour „REM-SB“ DC input not locked. It can be switched on by pushbutton “On/Off” normal (front panel) or via command from digital interface. inverted DC input locked.
EL 9000 B HP Series 3.6 Alarms and monitoring 3.6.1 Definition of terms There is a clear distinction between equipment alarms (see „3.3. Alarm conditions“) such as overvoltage or overheating, and user defined events such as e.g OCD (overcurrent supervision). Whilst device alarms primarily serve to protect the connected DC source by switching the DC input off, user defined events can do the same (action = ALARM), but can also simply give an acoustic signal to make the user aware.
EL 9000 B HP Series Some device alarms are configurable: Alarm Meaning Description Range Indication OVP OverVoltage Triggers an alarm if the DC input voltage reaches the Display, analog & 0 V...1.03*UNom Protection defined threshold. The DC input will be switched off.. digital interface OCP OverCurrent Triggers an alarm if the DC input current reaches the 0 A....1.1*INom Protection defined threshold. The DC input will be switched off..
EL 9000 B HP Series 3.6.2.1 User defined events The monitoring functions of the device can be configured for user defined events. By default, events are deactivated (action = NONE). Contrary to device alarms, the events only work while the DC input is switched on. It means, for instance, that you cannot detect undervoltage (UVD) anymore after switching the DC input off and the voltage is still sinking.
EL 9000 B HP Series 3.7 Control panel (HMI) lock In order to avoid the accidental alteration of a value during manual operation, the rotary knobs or the touchscreen can be locked so that no alteration of values will be accepted without prior unlocking. ►►How to lock the HMI 1. In the main page, tap the lock symbol (upper right corner). 2.
EL 9000 B HP Series 3.9 Loading and saving a user profile The menu “Profiles” serves to select between a default profile and up to 5 user profiles. A profile is a collection of all settings and set values. Upon delivery, or after a reset, all 6 profiles have the same settings and all set values are 0. If the user changes settings or sets target values then these create a working profile which can be saved to one of the 5 user profiles. These profiles or the default one can then be switched.
EL 9000 B HP Series 3.10 The function generator 3.10.1 Introduction The built-in function generator is able to create various signal forms and apply these to the set value of voltage or current. The standard functions are based on an arbitrary generator and directly accessible and configurable using manual control. For remote control, the fully customisable arbitrary generator replicates the functions with sequences containing 8 parameters each.
EL 9000 B HP Series 3.10.4 Manual operation 3.10.4.1 Function selection and control Via the touchscreen one of the functions described in 3.10.1 can be called up, configured and controlled. Selection and configuration are only possible when the input is switched off. ►►How to select a function and adjust parameters 1. While the DC input is switched off tap touch area on the main screen. 2. In the menu overview tap on the touch area and then on the desired function. 3.
EL 9000 B HP Series ►►How to start and stop a function 1. The function can be started either by tapping or pushing the “On/Off” button, if the DC input is currently switched off. The function then starts immediately. In case START is used while the DC input is still switched off, the DC input will be switched on automatically. 2. The function can be stopped either by tapping or pushing the “On/Off” button.
EL 9000 B HP Series Schematic diagram: Application and result: A triangular wave signal for input current (direct) or input voltage (indirect) is generated. The positive and negative slope times are variable and can be set independently. A The offset shifts the signal on the Y-axis. Amplitude The sum of the intervals t1 and t2 gives the cycle time and its reciprocal is the frequency. Offset Example: a frequency of 10 Hz is required and would lead to periodic duration of 100 ms.
EL 9000 B HP Series 3.10.8 Trapezoidal function The following parameters can be configured for a trapezoidal curve function: Value Range I(A), U(A) 0...(Nominal value - (Offs)) of U, I A = Amplitude of the signal to be generated Description I(Offs), U(Offs) 0...(Nominal value - (A)) of U, I Offs = Offset, based on the foot of the trapezium t1 0.01 ms...36000 s Time for the negative slope of the trapezoidal wave signal t2 0.01 ms...
EL 9000 B HP Series 3.10.10 Arbitrary function The arbitrary (freely definable) function offers the user further scope. Up to 100 sequences are available for use for current I and voltage U, all of which have the same parameters but which can be differently configured so that a complex function process can be built up. The 100 sequences can run one after another in a sequence block, and this sequence block can then be repeated many times or endlessly.
EL 9000 B HP Series Schematic diagram: Applications and results: A Focussing 1 cycle of 1 sequence from 100: End (DC) Start (DC) St ar t( En d AC ) (A C) Example 2 t The DC values at start and end are the same but the AC (amplitude) not. The end value is higher than the start so that the amplitude increases with each new half sine wave continuously through the sequence. This, of course, only if the sequence time and frequency allow for multiple waves to be created. e.g. for f=1 Hz and Seq.
EL 9000 B HP Series By linking together a number of differently configured sequences, complex progressions can be created. Smart configuration of the arbitrary generator can be used to match triangular, sine, rectangular or trapezoidal wave functions and thus, e.g. a sequence of rectangular waves with differing amplitudes or duty cycles could be produced. Assignment to U or I makes 100 sequences available for the use on either current or voltage, but not on a mix of both.
EL 9000 B HP Series 3.10.10.1 Loading and saving the arbitrary function The 100 sequences of the arbitrary function, which can be manually configured with the control panel of the device and which are applicable either to voltage (U) or current (I), can be saved to or loaded from a common USB stick via the front side USB port. Generally, all 100 sequences are saved or loaded using a text file of type CSV (semicolon separator), which represents a table of values.
EL 9000 B HP Series ►►How to save a sequence table (100 sequences) to an USB stick 1. Do not plug the USB stick yet or remove it. 2. Access the function selection menu of the function generator via MENU -> Function Generator -> Arbitrary 3. Tap on , then . The device will request you to plug the USB stick now. 4. After plugging it, the device will try to access the USB stick and find the folder HMI_FILES and read the content.
EL 9000 B HP Series Uploading of a table from an USB stick must use text files in CSV format (.csv). Plausibility is checked on loading (values not too high, number of values correct),and possible errors reported in which case the table will not be loaded. The 4096 values in the table are only checked for size and count. If all the values were to be graphically plotted a curve would be created which could include significant step changes in current or voltage.
EL 9000 B HP Series 3.10.13 Battery test function The purpose of the battery test function is to discharge various battery types in industrial product tests or laboratory applications. It is only available via access on the HMI, at least as setup and use are described below, but can also be achieved in remote control using the arbitrary function generator. The only disadvantage in remote control are the missing counters of battery capacity (Ah), energy (Wh) and time.
EL 9000 B HP Series 3.10.13.3 Global parameters Parameter Range Description Discharge voltage 0...Nominal value of U Variable voltage threshold to make the test stop when reached (is connected to the battery voltage on the DC input of the load) Discharge time 0...10 h Maximum test time after which the test can stop automatically Discharge capacity 0...
EL 9000 B HP Series 3.10.13.6 Possible reasons for battery test stop The battery test function run can be stopped by different reasons: • • • • • Manual stop on the HMI with touch area STOP After the max. test time has been reached and action “End of test” was set for it After the max.
EL 9000 B HP Series 3.10.14.2 Mode MPP2 This mode tracks the MPP, so it is closest to the operation of a solar inverter. Once the MPP is found, the function won’t stop, but try to track the MPP permanently. Due to the nature of solar panels this can only be done below the level of the MPP. As soon as this point is reached, the voltage starts to sink further and so does the actual power.
EL 9000 B HP Series 3.10.15 Remote control of the function generator The function generator can be remotely controlled but configuration and control of the functions with individual commands is different from manual operation. The external documentation “Programming Guide ModBus & SCPI” explains the approach.
EL 9000 B HP Series 3.11 Other applications 3.11.1 Series connection Series connection is not a permissible operating method for electronic loads and must not be installed or operated under any circumstances! 3.11.2 Parallel operation in master-slave (MS) Multiple devices of same kind and model can be connected in parallel in order to create a system with higher total current and hence higher power.
EL 9000 B HP Series ►►How to connect the master-slave bus 1. Switch off all units that are to be connected and connect them together with a network cable (CAT3 or bet2. 3. ter, not included). It doesn’t matter which of the two master-slave connection sockets (RJ45, backside) is connected to the next unit. Also connect all units at the DC side. The two units at the beginning and end of the chain should be terminated, if long connection cables are used.
EL 9000 B HP Series 3.11.2.5 Operating the master-slave system After successful configuration and initialisation of the master and slave units, these will show their status in the displays.
EL 9000 B HP Series • If the master unit is switched off on the AC side (power switch, supply undervoltage) and comes back later, it will automatically initialise the MS system again, finding and integrating all active slaves. In this case, MS can be restored automatically. • If accidentally multiple or no units are defined as master the master-slave system cannot be initialised.
EL 9000 B HP Series 3.11.3 Two quadrants operation (2QO) 3.11.3.1 Introduction This kind of operation refers to the use of a source, in this case a power supply from a compatible series (see section „1.9.9. “Share” connector“) and a sink, in this case a series EL 9000 B HP electronic load. The source and the sink function alternately in order to test a device, such as a battery, by deliberate charging and discharging as part of a functional test, or a motor by clipping excess energy with the sink.
EL 9000 B HP Series 3.11.3.3 Settings on the devices The master-slave settings in the MENU also affect the Share bus. For correct 2QO operation, all involved load units must be slaves on the Share bus. This is achieved by setting the master-slave mode to OFF or SLAVE, depending on if there is digital master-slave in use or not. For the one load that is master (setting: MASTER) in the master-slave system the additional parameter “PSI/ELR system” has to be activated.
EL 9000 B HP Series 4. Service and maintenance 4.1 Maintenance / cleaning The device needs no maintenance. Cleaning may be needed for the internal fans, the frequency of cleanse is depending on the ambient conditions. The fans serve to cool the components which are heated by the inherent dissipation of energy. Heavily dirt filled fans can lead to insufficient airflow and therefore the DC input would switch off too early due to overheating or possibly lead to defects.
EL 9000 B HP Series 4.3 Calibration 4.3.1 Preface The devices of series EL 9000 B HP feature a function to re-adjust the most important input related values when doing a calibration and in case these values have moved out of tolerance. The re-adjustment is limited to compensate small differences of up to 1% or 2% of the max. value. There are several reasons which could make it necessary to re-adjust a unit: component aging, component deterioration, extreme ambient conditions, high frequent use.
EL 9000 B HP Series 4.3.3.1 Set values ►►How to calibrate the voltage 1. Adjust the connected voltage source to approx. 102% of the maximum 2. voltage specified for the EL device. For the example with an 80 V EL this would be 81.6 V for the source. Set the current limitation of the voltage source to 5% of the nominal current specified for EL device, for this example it is 8.5 A. Check again, that for voltage calibration, the sensing connector on the rear of the device is not connected.
EL 9000 B HP Series 4.3.3.3 Save and exit After calibration you may furthermore enter the current date as “calibration date” by tapping selection screen and enter the date in format YYYY / MM / DD. Last but not least save the calibration data permanently by tapping in the . Leaving the calibration selection menu without “Save and exit” will discard calibration data and the procedure would have to be repeated! 5. Contact and support 5.
EA-Elektro-Automatik GmbH & Co. KG Development - Production - Sales Helmholtzstraße 31-37 41747 Viersen Germany Fon: 02162 / 37 85-0 ea1974@elektroautomatik.de www.elektroautomatik.