User manual
Page 10
ELR 9000 Series
www.elektroautomatik.de
ea1974@elektroautomatik.de
EA Elektro-Automatik GmbH
Helmholtzstr. 31-33 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
1.8.3 Specic technical data
(1 Related to the nominal values, the accuracy denes the maximum deviation between an adjusted values and the true (actual) value.
Example: a 80 V model has min. 0.3% voltage accuracy, that is 240 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 240 mV, which
means it might be between 4.76 V and 5.24 V.
(2 Typical value at 100% input voltage and 100% power
3) Set values as in the display or as data readable via digital interfaces are more accurate than the corresponding value on the DC input. Their accuracy subtracts
from the general accuracy. For actual values it is vice versa. There the display accuracy adds to the general accuracy, so the error (i.e. deviation) will be higher.
3.5 kW
Model
ELR 9080-170 ELR 9250-70 ELR 9500-30 ELR 9750-22
AC Input/Output
Input/output voltage 195...253 V L-N 195...253 V L-N 195...253 V L-N 195...253 V L-N
Input/output connection L,N,PE L,N,PE L,N,PE L,N,PE
Input/output frequency 50/60 Hz ±10% 50/60 Hz ±10% 50/60 Hz ±10% 50/60 Hz ±10%
Input/output fuse (internal) T16 A T16 A T16 A T16 A
Efciency
(2
92.5% 93.5% 94.5% 94.5%
DC Input
Max. input voltage U
Max
80 V 250 V 500 V 750 V
Max. input power P
Max
3500 W 3500 W 3500 W 3500 W
Max. input current I
Max
170 A 70 A 30 A 22 A
Overvoltage protection range 0...1.1 * U
Max
0...1.1 * U
Max
0...1.1 * U
Max
0...1.1 * U
Max
Overcurrent protection range 0...1.1 * I
Max
0...1.1 * I
Max
0...1.1 * I
Max
0...1.1 * I
Max
Overpower protection range 0...1.1 * P
Max
0...1.1 * P
Max
0...1.1 * P
Max
0...1.1 * P
Max
Max. allowed input voltage 100 V 300 V 600 V 850 V
Min. input voltage for I
Max
0.73 V 2.3 V 4.6 V 6.8 V
Temperature coefcient for set
values Δ / K
Voltage / current: 100 ppm
Voltage regulation
Adjustment range 0...80 V 0...250 V 0...500 V 0...750 V
Stability at ±10% ΔU
AC
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
Stability at ΔI < 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Accuracy
(1
(at 23 ± 5°C) < 0.3% U
Max
< 0.3% U
Max
< 0.3% U
Max
< 0.3% U
Max
Display: Adjustment resolution see section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(3
≤ 0.2%
Remote sensing compensation max. 5% U
Max
Current regulation
Adjustment range 0...170 A 0...70 A 0...30 A 0...22 A
Stability at ±10% ΔU
AC
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
Stability at ΔU < 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
Accuracy
(1
(at 23 ± 5°C) < 0.4% I
Max
< 0.4% I
Max
< 0.4% I
Max
< 0.4% I
Max
Display: Adjustment resolution see section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(3
≤0.2%
Compensation 10-90% ΔU
DC
< 0.6 ms < 0.6 ms < 0.6 ms < 0.6 ms
Power regulation
Adjustment range 0…3500 W 0…3500 W 0…3500 W 0…3500 W
Stability at ±10% ΔU
AC
< 0.05% < 0.05% < 0.05% < 0.05%
Stability at ΔI / ΔU < 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
Accuracy
(1
(at 23 ± 5°C) < 1.25% P
Max
< 1.5% P
Max
< 1.4% P
Max
< 1.5% P
Max
Display: Adjustment resolution see section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(3
≤ 0.2%
Resistance regulation
Adjustment range 0.01…12 Ω 0.09…120 Ω 0.42…480 Ω 0.8…1100 Ω
Accuracy
(at 23 ± 5°C) ≤2% of max. resistance ± 0.3% of maximum current
Display: Adjustment resolution see section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(3
≤0.2%