User manual
40
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
© 2008, Elektro-Automatik GmbH & Co. KG
Handling the Gerätes
CAN Baud rate
Possible settings: 10kBd, 20KBd, 50kBd, 100kBd, 125kBd,
250kBd, 500kBd, 1MBd
Default setting: 100kBd
Belongs to: CAN interface card IF-C1
Explanation: determines the baudrate (transmission speed)
of the CAN bus. If you connect the CAN card to an existing
network, you got to set the same baudrate here as the bus
is using, becaus any device in a bus has to use the same
bus speed.
CAN Relocatable ID
Possible settings: 0...31
Default setting: 0
Belongs to: CAN interface card IF-C1
Explanation: this determines the (relocatable) address seg-
ment, in which the device node of the CAN is located. For
further information refer to basic CAN topology datasheets.
Example: if the electronic load has to be assigned to address
5 by certain reasons and this would collide with another
bus member with the same address, you can move the
addresstoanothersegmentbydeningtheRID(shortfor
relocatable ID), so that no collision can occur. Hence there
are, theoretically, 32 x 30 possible device nodes available
when using CAN.
CAN Bus terminate
Possible settings: yes, no
Default setting: no
Belongs to: CAN interface card IF-C1
Explanation:denes,ifthebusterminationresistoronthe
CAN interface card is active or not. This is only required if
the CAN card is in that particular device which is located
at the end of a CAN bus. By setting this parameter to yes
the resistor is activated, no deactivates it. In case you don‘t
want to use this feature and instead want to install a custom
resistor for bus termination, make sure that this setting is
set to no.
RS232 Baud rate
Possible settings: 9600 Bd, 19200 Bd, 38400 Bd, 57600 Bd
Default setting: 57600 Bd
Belongs to: RS232 interface card IF-R1
Explanation: determines the baudrate (transmission speed)
of the serial data transmission when using the serial RS232
interface card IF-R1. Make sure, that the other end of the
serial connection operates at the same baudrate.
7. Deviceconguration
7.1 The setup menu
The setup menu can activated anytime by the selector Le-
vel(3), except during remote control mode (by interface card)
or external mode (analogue interface). While the load is in
setup, no normal load operation is possible.
The display shows a certain number of parameters, depen-
ding on which interface card is installed. The parameters are
selected by Selection(5) and changed with Setting(6). Two
small triangles on the right side of the display indicate that
multiple parameters are available. The display furthermore
showsthetypestringoftheinstalledcardintherstline,for
example IF-U1, if one is equipped:
The second line subsequently shows all parameters which
are selected by Selection(5). The number of parameters
varies according to the equipped interface card. The following
overview lists the possible parameter and its settings:
Trigger mode
Possible settings: internal, external
Default setting: internal
Belongs to: Device
Explanation:denes,ifthetriggersignalfortheLevelA/B
operation, which effects the change between A and B, is
automatically generated by the device (internal) or if it‘s put
in by the trigger input (external).
Device node
Possible settings: 1...30
Default setting: 1
Belongs to: Device
Explanation: denes thedevice node(or address) of the
device in order to distinct between mutliple devices in a net-
work and to address it correctly. 30 addresses are available
which means that up to 30 devices can be controlled from
one PC. Every address must only be given once in a system
of connected devices.
Keep set values
Possible settings: yes, no
Default setting: no
Belongs to: Device
Explanation: yes denes, that the set values which are
adjusted by the user are kept when switching the regulation
mode (also see „6.6 Selecting the regulation mode“), while
no denesthatthesetvaluesarealwaysresettodefault
values when switching.
Figure 15