User manual
28
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
© 2008, Elektro-Automatik GmbH & Co. KG
About the device
2.2Devicespecicdata
Mains input
Mains voltage 115V/230V switchable 115V/230V switchable 115V/230V switchable
Mains frequency 50/60Hz 50/60Hz 50/60Hz
Mains fuse T2,5A T2,5A T2,5A
DC input
Input voltage U
nom
0…80V 0…160V 0…400V
Input power P
nom
0...2400W,
with temperature related derating
0...2400W,
with temperature related derating
0...2400W,
with temperature related derating
- permanent power
1500W at 20°C ambient 1500W at 20°C ambient 1500W at 20°C ambient
Input current I
nom
0…200A 0…100A 0…50A
Overvoltage protection threshold
1,1 * U
nom
1,1 * U
nom
1,1 * U
nom
max. allowed input voltage 100V 180V 500V
Voltage control
Adjustment range 0…80V 0…160V 0…400V (0...450V)
Display resolution 100mV 100mV 100mV
Accuracy**
<0.1% of U
nom
<0.1% of U
nom
<0.1% of U
nom
Current control
Adjustment range 0…200A 0…100A 0…50A
Display resolution 100mA 100mA 10mA
Accuracy**
<0.2% of I
nom
<0.2% of I
nom
<0.2% of I
nom
Power control
Adjustment range 0…2400W 0…2400W 0…2400W
Display resolution 1W 1W 1W
Accuracy**
<2% of P
nom
<2% of P
nom
<2% of P
nom
Resistance control
Adjustment range 1 «ȍ 0…10 «ȍ
Display resolution Pȍ Pȍ Pȍ
Accuracy**
<2% of resistance range,
0.3% of range of current
<2% of resistance range,
0.3% of range of current
<2% of resistance range,
0.3% of range of current
Adjustment range 2 «ȍ «ȍ «ȍ
Display resolution Pȍ Pȍ Pȍ
Accuracy**
<2% of resistance range,
0.3% of range of current
<2% of resistance range,
0.3% of range of current
<2% of resistance range,
0.3% of range of current
Dynamic values
Current rise and fall time*** <50us <50us <50us
Level 2 adjustable levels per control mode 2 adjustable levels per control mode 2 adjustable levels per control mode
Times (pulsed operation) 2 adjustable, 50us..100s 2 adjustable, 50us..100s 2 adjustable, 50us..100s
Rise/fall time adjustable, 30us…200ms adjustable, 30us…200ms adjustable, 30us…200ms
Accuracy** <10% <10% <10%
Trigger input* yes, for external level switching yes, for external level switching yes, for external level switching
Battery test feature
Modes Current/Power/Resistance Current/Power/Resistance Current/Power/Resistance
Battery protection Discharge threshold voltage adjustable Discharge threshold voltage adjustable Discharge threshold voltage adjustable
Display Time and comsumed battery capacity Time and comsumed battery capacity Time and comsumed battery capacity
Display
2 x 40 characters, illuminated 2 x 40 characters, illuminated 2 x 40 characters, illuminated
Analogue interface*
Set value inputs 0...10V for U / I / P / R (0...100% set value) 0...10V for U / I / P / R (0...100% set value) 0...10V for U / I / P / R (0...100% set value)
Monitor outputs 0...10V for U / I (0...100% actual value) 0...10V for U / I (0...100% actual value) 0...10V for U / I (0...100% actual value)
Control signals LQWHUQDOH[WHUQDO,QSXWRQRII50RGHȍ LQWHUQDOH[WHUQDO,QSXWRQRII50RGHȍ LQWHUQDOH[WHUQDO,QSXWRQRII50RGHȍ
Error signals Overvoltage / Overtemperature Overvoltage / Overtemperature Overvoltage / Overtemperature
Outputs Reference voltage Reference voltage Reference voltage
Cooling
Type Temperature controlled fans Temperature controlled fans Temperature controlled fans
Ambient temperature 0…70°C with derating 20W/°C 0…70°C with derating 20W/°C 0…70°C with derating 20W/°C
Terminals
Load input Rear side, M8 screw terminals Rear side, M8 screw terminals Rear side, M8 screw terminals
System Bus Rear side, 7pole screw clamp Rear side, 7pole screw clamp Rear side, 7pole screw clamp
Analogue interface Rear side, 15pole Sub-D socket Rear side, 15pole Sub-D socket Rear side, 15pole Sub-D socket
Dimensions W x H x D
19" x 2U x 460mm 19" x 2U x 460mm 19" x 2U x 460mm
Weight
15,9kg 15,9kg 15,9kg
Article number
33 200 230 33 200 233 33 200 236
Supported interface cards
CAN, USB, RS232, GPIB CAN, USB, RS232, GPIB CAN, USB, RS232, GPIB
* for technical specification see section "Analogue interface"
*** Rise and fall time are defined at 10%...90% and 90%...10% of the nominal value
All single values, which specify a tolerance are typical values
EL 9160-100
** Accuracy is defined by the difference between actual value (eg. of the output voltage) and the adjusted set value, without taking regard
of temperature errors or component deterioration
EL9400-50 (S01)
EL9080-200