Instructions
Page 10
PS 9000 1U Series
www.elektroautomatik.de
ea1974@elektroautomatik.de
EA Elektro-Automatik GmbH
Helmholtzstr. 31-33 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
1.8.3 Specic technical data
1500 W
Model 1U
PS 9080-50 PS 9200-25 PS 9360-15 PS 9500-10 PS 9750-06
AC Input
Input voltage 100...264 V AC 100...264 V AC 100...264 V AC 100...264 V AC 100...264 V AC
Input connection 1ph,N,PE 1ph,N,PE 1ph,N,PE 1ph,N,PE 1ph,N,PE
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Input fuse (internal) T16 A T16 A T16 A T16 A T16 A
Leak current < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA
Power factor ~ 0.99 ~ 0.99 ~ 0.99 ~ 0.99 ~ 0.99
Idle mode power consumption ~ 70 W ~ 70 W ~ 70 W ~ 70 W ~ 70 W
DC Output
Max. output voltage U
Max
80 V 200 V 360 V 500 V 750 V
Max. output current I
Max
50 A 25 A 15 A 10 A 6 A
Max. output power P
Max
1500 W 1500 W 1500 W 1500 W 1500 W
Overvoltage protection range 0...88 V 0...220 V 0...396 V 0...550 V 0...825 V
Overcurrent protection range 0...55 A 0...27,5 A 0...17,6 A 0...11 A 0...6,6 A
Overpower protection range 0…1650 W 0…1650 W 0…1650 W 0…1650 W 0…1650 W
Temperature coefcient Voltage / current: 100 ppm/K
Voltage regulation
Adjustment range 0...81.6 V 0...204 V 0...367.2 V 0...510 V 0...765 V
Accuracy
(1
(at 23 ± 5°C) < 0.1% U
Nenn
< 0.1% U
Nenn
< 0.1% U
Nenn
< 0.1% U
Nenn
< 0.1% U
Nenn
Line regulation at ±10% ΔU
AC
< 0.02% U
Nenn
< 0.02% U
Nenn
< 0.02% U
Nenn
< 0.02% U
Nenn
< 0.02% U
Nenn
Load regulation at 0...100% load < 0.05% U
Nenn
< 0.05% U
Nenn
< 0.05% U
Nenn
< 0.05% U
Nenn
< 0.05% U
Nenn
Rise time 10...90% ΔU Max. 15 ms Max. 15 ms Max. 15 ms Max. 15 ms Max. 15 ms
Compensation 10%->90% load < 1.7 ms < 1.4 ms < 2.2 ms < 2 ms < 2 ms
Display: Resolution See section „1.9.4.4. Resolution of the displayed values“
Display: Accuracy
(3
≤ 0.2% U
Nom
≤ 0.2% U
Nom
≤ 0.2% U
Nom
≤ 0.2% U
Nom
≤ 0.2% U
Nom
Ripple
(2
< 100 mV
PP
< 5.2 mV
RMS
< 293 mV
PP
< 51 mV
RMS
< 195 mV
PP
< 33 mV
RMS
< 293 mV
PP
< 63 mV
RMS
< 260 mV
PP
< 40 mV
RMS
Remote sensing compensation Max. 5% U
Nenn
Max. 5% U
Nenn
Max. 5% U
Nenn
Max. 5% U
Nenn
Max. 5% U
Nenn
Fall time (at no load) after
switching DC output off
Down from 100% to <60 V: less than 10 s
Current regulation
Adjustment range 0...51 A 0...25.5 A 0...15.3 A 0...10.2 A 0...6.12 A
Accuracy
(1
(at 23 ± 5°C) < 0.2% I
Nom
< 0.2% I
Nom
< 0.2% I
Nom
< 0.2% I
Nom
< 0.2% I
Nom
Line regulation at ±10% ΔU
AC
< 0.05% I
Nom
< 0.05% I
Nom
< 0.05% I
Nom
< 0.05% I
Nom
< 0.05% I
Nom
Load regulation at 0...100% ΔU
OUT
< 0.15% I
Nom
< 0.15% I
Nom
< 0.15% I
Nom
< 0.15% I
Nom
< 0.15% I
Nom
Ripple
(2
< 75 mA
PP
< 29 mA
PP
< 10 mA
PP
< 9.2 mA
PP
< 4.1 mA
PP
Display: Resolution See section „1.9.4.4. Resolution of the displayed values“
Display: Accuracy
(3
≤ 0.2% I
Nom
≤ 0.2% I
Nom
≤ 0.2% I
Nom
≤ 0.2% I
Nom
≤ 0.2% I
Nom
Power regulation
Adjustment range 0…1530 W 0…1530 W 0…1530 W 0…1530 W 0…1530 W
Accuracy
(1
(at 23 ± 5°C) < 1% P
Nom
< 1% P
Nom
< 1% P
Nom
< 1% P
Nom
< 1% P
Nom
Line regulation at ±10% ΔU
AC
< 0.05% P
Nom
< 0.05% P
Nom
< 0.05% P
Nom
< 0.05% P
Nom
< 0.05% P
Nom
Load regulation at 10-90% ΔU*ΔI < 0.75% P
Nom
< 0.75% P
Nom
< 0.75% P
Nom
< 0.75% P
Nom
< 0.75% P
Nom
Display: Resolution See section „1.9.4.4. Resolution of the displayed values“
Efciency at 100% U
DC
~ 91% ~ 93% ~ 94% ~ 94% ~ 95%
Efciency at 100% I
DC
~ 89% ~ 90% ~ 92% ~ 92% ~ 94%
(1 Related to the nominal values, the accuracy denes the maximum deviation between an adjusted values and the true (actual) value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 The display error adds to the error of the related actual value on the DC output