2.3.7 Connection of remote sensing
Both pins „NC“ of the Sense connector must not be wired!
• The cross section of the sense cables is noncritical. However, it should be increased with
increasing cable length. Recommendation: for cables up to 5 m use at least 0.5 mm²
• Sense cables should be twisted and laid close to the DC cables to damp oscillation. If neces-
sary, an additional capacitor should be installed at the load/consumer to eliminate oscillation
• The sense cables must be connected + to + and - to - at the load, otherwise both systems
may be damaged
• In master-slave operation, the remote sensing should be connected to the master unit only
Figure 7 - Example for remote sensing wiring