PS 9000 3U Series
15 kW
Model 208 V
PS 9750-60 PS 91000-40 PS 91500-30
Analog interface
(1
Set value inputs U, I, P
Actual value outputs U, I
Control signals DC on/o󰀨, remote control on/o󰀨
Status signals CV, OVP, OT, OCP, OPP, PF, DC on/o󰀨
Galvanic isolation to the device Max. 725 V DC
Sample rate of inputs 500 Hz
Insulation Allowed oat (potential shift) on the DC output:
Negative terminal to PE Max. ±725 V DC ±725 V DC ±725 V DC
Positive terminal to PE Max. +1000 V DC +1000 V DC +1800 V DC
Miscellaneous
Cooling Temperature controlled fans, front inlet, rear exhaust
Ambient temperature 0..50°C (32...122°F)
Storage temperature -20...70°C (-4...158°F)
Humidity < 80%, not condensing
Standards
EN 61010-1:2010
EMC TÜV approved acc. IEC 61000-6-2:2005 and IEC 61000-6-3:2006 Class B
Overvoltage category 2
Protection class 1
Pollution degree 2
Operational altitude <2000 m (1,242 mi)
Digital interfaces
Featured 1x USB-B, 1x Ethernet
(2
, 1x GPIB (optional with option 3W)
Galvanic isolation from device Max. 725 V DC
Connectors
Rear side Share Bus, DC output, AC input, remote sensing, analog interface, USB-B, Ethernet
Dimensions
Enclosure (WxHxD) 19“ x 3U x 682 mm (26.8”)
Total (WxHxD) 483 x 133 x 787 mm (19” x 5.2” x 31”)
Weight
30 kg (66.1 lb) 30 kg (66.1 lb) 30 kg (66.1 lb)
Article number
(3
06238268 06238270 06238269
(1 For technical specications of the analog interface see „3.5.4.4 Analog interface specication“ on page 58
(2 Only in the standard version