PS 9000 3U Series
10 kW / 15 kW
Model 208 V
PS 91000-30 PS 9080-510 PS 9200-210 PS 9360-120 PS 9500-90
Analog interface
(1
Set value inputs U, I, P
Actual value outputs U, I
Control signals DC on/o󰀨, remote control on/o󰀨
Status signals CV, OVP, OT, OCP, OPP, PF, DC on/o󰀨
Galvanic isolation to the device Max. 725 V DC
Sample rate of inputs 500 Hz
Insulation Allowed oat (potential shift) on the DC output:
Negative terminal to PE Max. ±725 V DC ±400 V DC ±400 V DC ±400 V DC ±725 V DC
Positive terminal to PE Max. +1000 V DC ±400 V DC +600 V DC +600 V DC +1000 V DC
Miscellaneous
Cooling Temperature controlled fans, front inlet, rear exhaust
Ambient temperature 0..50°C (32...122°F)
Storage temperature -20...70°C (-4...158°F)
Humidity < 80%, not condensing
Standards
EN 61010-1:2010
EMC TÜV approved acc. IEC 61000-6-2:2005 and IEC 61000-6-3:2006 Class B
Overvoltage category 2
Protection class 1
Pollution degree 2
Operational altitude <2000 m (1,242 mi)
Digital interfaces
Featured 1x USB-B, 1x Ethernet
(2
, 1x GPIB (optional with option 3W)
Galvanic isolation from device Max. 725 V DC
Connectors
Rear side Share Bus, DC output, AC input, remote sensing, analog interface, USB-B, Ethernet
Dimensions
Enclosure (WxHxD) 19“ x 3U x 682 mm (26.8”)
Total (WxHxD) 483 x 133 x 787 mm (19” x 5.2” x 31”)
Weight
24 kg (52.9 lb) 30 kg (66.1 lb) 30 kg (66.1 lb) 30 kg (66.1 lb) 30 kg (66.1 lb)
Article number
(3
06238262 06238264 06238265 06238266 06238267
(1 For technical specications of the analog interface see „3.5.4.4 Analog interface specication“ on page 58
(2 Only in the standard version
(3 Article number of the standard US version, devices with options will have a di󰀨erent number