Instructions
Page 19
EA Elektro-Automatik GmbH
Helmholtzstr. 31-37 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
ea1974@elektroautomatik.de
PS 9000 3U Series
5 kW
Model 208 V
PS 9080-170 PS 9200-70 PS 9360-40 PS 9500-30 PS 9750-20
Analog interface
(1
Set value inputs U, I, P
Actual value outputs U, I
Control signals DC on/o, remote control on/o
Status signals CV, OVP, OT, OCP, OPP, PF, DC on/o
Galvanic isolation to the device Max. 725 V DC
Sample rate of inputs 500 Hz
Insulation Allowed oat (potential shift) on the DC output:
Negative terminal to PE Max. ±400 V DC ±400 V DC ±400 V DC ±725 V DC ±725 V DC
Positive terminal to PE Max. +400 V DC +600 V DC +600 V DC +1000 V DC +1000 V DC
Miscellaneous
Cooling Temperature controlled fans, front inlet, rear exhaust
Ambient temperature 0..50°C (32...122°F)
Storage temperature -20...70°C (-4...158°F)
Humidity < 80%, not condensing
Standards
EN 61010-1:2010
EMC TÜV approved acc. IEC 61000-6-2:2005 and IEC 61000-6-3:2006 Class B
Overvoltage category 2
Protection class 1
Pollution degree 2
Operational altitude <2000 m (1,242 mi)
Digital interfaces
Featured 1x USB-B, 1x Ethernet
(2
, 1x GPIB (optional with option 3W)
Galvanic isolation from device Max. 725 V DC
Connectors
Rear side Share Bus, DC output, AC input, remote sensing, analog interface, USB-B, Ethernet
Dimensions
Enclosure (WxHxD) 19“ x 3U x 682 mm (26.8”)
Total (WxHxD) 483 x 133 x 787 mm (19” x 5.2” x 31”)
Weight
≈17 kg (37.5 lb) ≈17 kg (37.5 lb) ≈17 kg (37.5 lb) ≈17 kg (37.5 lb) ≈17 kg (37.5 lb)
Article number
(3
06238251 06238252 06238253 06238254 06238255
(1 For technical specications of the analog interface see „3.5.4.4 Analog interface specication“ on page 58
(2 Only in the standard version
(3 Article number of the standard US version, devices with options will have a dierent number