PS 9000 3U Series
1.8.4 Specic technical data (208 V AC models)
(1 Related to the nominal values, the accuracy denes the maximum deviation between an adjusted values and the true (actual) value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to dier max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 Typical value at 100% output voltage and 100% power
(4 The display error adds to the error of the related actual value on the DC output
5 kW
Model 208 V
PS 9080-170 PS 9200-70 PS 9360-40 PS 9500-30 PS 9750-20
AC Input
Voltage (L-L) 208 V, ± 10%, 45 - 65 Hz
Input connection 2ph,PE 2ph,PE 2ph,PE 2ph,PE 2ph,PE
Leak current < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA
Power factor > 0.99 > 0.99 > 0.99 > 0.99 > 0.99
DC Output
Max. output voltage U
Max
80 V 200 V 360 V 500 V 750 V
Max. output current I
Max
170 A 70 A 40 A 30 A 20 A
Max. output power P
Max
5 kW 5 kW 5 kW 5 kW 5 kW
Overvoltage protection range 0...88 V 0...220 V 0...396 V 0...550 V 0...825 V
Overcurrent protection range 0...187 A 0...77 A 0...44 A 0...33 A 0...22 A
Overpower protection range 0…5.5 kW 0…5.5 kW 0…5.5 kW 0…5.5 kW 0…5.5 kW
Temperature coecient for set
values Δ/K
Voltage / current: 100 ppm
Output capacitance (approx.) 8500 μF 2500 μF 400 μF 250 μF 100 μF
Voltage regulation
Adjustment range 0...81.6 V 0...204 V 0...367.2 V 0...510 V 0...765 V
Accuracy
(1
(at 23±5°C / 73±9°F)) < 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
Line regulation at ±10% ΔU
AC
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
Load regulation at 0...100% load < 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Rise time 10...90% Max. 30 ms Max. 30 ms Max. 30 ms Max. 30 ms Max. 30 ms
Settling time after load step < 1.5 ms < 1.5 ms < 1.5 ms < 1.5 ms < 1.5 ms
Display: Resolution See section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
Ripple
(2
< 200 mV
PP
< 16 mV
RMS
< 300 mV
PP
< 40 mV
RMS
< 550 mV
PP
< 65 mV
RMS
< 350 mV
PP
< 70 mV
RMS
< 800 mV
PP
< 200 mV
RMS
Remote sensing compensation Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Fall time at no load after switching
DC output o
Down from 100% to <60 V: less than 10 s
Current regulation
Adjustment range 0...173.4 A 0...71.4 A 0...40.8 A 0...30.6 A 0...20.4 A
Accuracy
(1
(at 23±5°C / 73±9°F)) < 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
Line regulation at ±10% ΔU
AC
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
Load regulation at 0...100% ΔU
OUT
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
Ripple
(2
< 80 mA
RMS
< 22 mA
RMS
< 5.2 mA
RMS
< 16 mA
RMS
< 16 mA
RMS
Display: Resolution See section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
Power regulation
Adjustment range 0…5.1 kW 0…5.1 kW 0…5.1 kW 0…5.1 kW 0…5.1 kW
Accuracy
(1
(at 23±5°C / 73±9°F)) < 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
Line regulation at ±10% ΔU
AC
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
Load reg. at 10-90% ΔU
OUT
* ΔI
OUT
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
Display: Resolution See section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.8% P
Max
≤ 0.8% P
Max
≤ 0.8% P
Max
≤ 0.8% P
Max
≤ 0.8% P
Max
Eciency
(3
≈ 93% ≈ 95% ≈ 95% ≈ 95,5% ≈ 94%