Datasheet

Irrtümer und Änderungen vorbehalten / Subject to modication without notice, errors and omissions excepted
© EA-Elektro-Automatik GmbH, 2013
54
EA-PS 9000 3U 3.3KW - 150KW
HOCHLEISTUNGS-DC-LABORNETZGERÄTE / HEAVY DUTY LABORATORY DC POWER SUPPLIES
Technische Daten Technical Data PS 9040-170 3U PS 9080-170 3U PS 9200-70 3U PS 9360-40 3U
Ausgangsspannung DC Output voltage DC 0...40V 0...80V 0...200V 0...360V
- Restwelligkeit
(1
- Ripple
(1
<100mV
PP
<10mV
RMS
<100mV
PP
<10mV
RMS
<200mV
PP
<25mV
RMS
<250mV
PP
<50mV
RMS
- Fernfühlungsausregelung -Sensing compensation ~ 1V ~ 2V ~ 5V ~ 7.5V
Ausgangsstrom Output current 0...170A 0...170A 0...70A 0...40A
- Restwelligkeit
(1
- Ripple BWL
(1
<528mA
PP
<106mA
RMS
<300mA
PP
<40mA
RMS
<44mA
PP
<11mA
RMS
<32mA
PP
<6.5mA
RMS
Ausgangsleistung Output power 0...3300W 0...5000W 0...5000W 0...5000W
Wirkungsgrad Efficiency ~93% ~93% ~95% ~93%
Programmierung U (typ.) Programming U (typ.) 1mV 1.5mV 4mV 7mV
Programmierung I (typ.) Programming I (typ.) 3.5mA 3.5mA 1.5mA 1mA
Programmierung P (typ.) Programming P (typ.) 0.27W 0.27W 0.27W 0.27W
Gewicht
(2
Weight
(2
19.8kg 19.8kg 19.8kg 19.8kg
Artikelnummer Article number 06230250 06230251 06230252 06230253
Technische Daten Technical Data PS 9500-30 3U PS 9750-20 3U PS 9040-340 3U PS 9040-510 3U
Ausgangsspannung DC Output voltage DC 0...500V 0...750V 0...40V 0...40V
- Restwelligkeit
(1
- Ripple
(1
<250mV
PP
<70mV
RMS
<600mV
PP
<120mV
RMS
<150mV
PP
<10mV
RMS
<150mV
PP
<10mV
RMS
- Fernfühlungsausregelung -Sensing compensation ~ 10V ~ 15V ~ 1V ~ 1V
Ausgangsstrom Output current 0...30A 0...20A 0...340A 0...510A
- Restwelligkeit
(1
- Ripple
(1
<14mA
PP
<8mA
RMS
<18mA
PP
<4mA
RMS
<600mA
PP
<80mA
RMS
<900mA
PP
<120mA
RMS
Ausgangsleistung Output power 0...5000W 0...5000W 0...6600W 0...10000W
Wirkungsgrad Efficiency ~95.5% ~94% ~93% ~93%
Programmierung U (typ.) Programming U (typ.) 10mV 15mV 1mV 1mV
Programmierung I (typ.) Programming I (typ.) 0.8mA 0.5mA 6.5mA 10mA
Programmierung P (typ.) Programming P (typ.) 0.29W 0.29W 0.27W 0.55W
Gewicht
(2
Weight
(2
19.8kg 19.8kg 25.5kg 25.5kg
Artikelnummer Article number 06230254 06230255 06230256 06230263
Technische Daten Technical Data PS 9080-340 3U PS 9200-140 3U PS 9360-80 3U PS 9500-60 3U
Ausgangsspannung DC Output voltage DC 0...80V 0...200V 0...360V 0...500V
- Restwelligkeit
(1
- Ripple
(1
<150mV
PP
<10mV
RMS
<200mV
PP
<25mV
RMS
<300mV
PP
<50mV
RMS
<300mV
PP
<70mV
RMS
- Fernfühlungsausregelung -Sensing compensation ~ 2V ~ 5V ~ 7.5V ~ 10V
Ausgangsstrom Output current 0...340A 0...140A 0...80A 0...60A
- Restwelligkeit
(1
- Ripple
(1
<600mA
PP
<80mA
RMS
<89mA
PP
<22mA
RMS
<77mA
PP
<13mA
RMS
<33mA
PP
<16mA
RMS
Ausgangsleistung Output power 0...10000W 0...10000W 0...10000W 0...10000W
Wirkungsgrad Efficiency ~93% ~95% ~93% ~95%
Programmierung U (typ.) Programming U (typ.) 1.5mV 4mV 7mV 10mV
Programmierung I (typ.) Programming I (typ.) 7mA 3mA 2mA 1.5mA
Programmierung P (typ.) Programming P (typ.) 0.55W 0.55W 0.55W 0.55W
Gewicht
(2
Weight
(2
25.5kg 25.5kg 25.5kg 25.5kg
Artikelnummer Article number 06230257 06230258 06230259 06230260
(1 RMS-Wert: NF 0...300KHz, PP-Wert: HF 0...20MHz / RMS value: LF 0...300kHz, PP value: HF 0...20MHz
(2 der Standardversion, Modelle mit Optionen können abweichen / of standard version, models with options may vary