1.8.3 Specic technical data
1000 W
Model 2U
PS 9040-40 PS 9080-40 PS 9200-15
AC Input
Input voltage & frequency 90...264 V AC, 50/60 Hz
Input connection 1ph (L ,N, PE)
Input fuse (internal) T16 A
Leak current < 3.5 mA
Power factor ~ 0.99
DC Output
Max. output voltage U
Max
40 V 80 V 200 V
Max. output current I
Max
40 A 40 A 15 A
Max. output power P
Max
1000 W 1000 W 1000 W
Overvoltage protection range 0...44 V 0...88 V 0...220 V
Overcurrent protection range 0...44 A 0...44 A 0...16.5 A
Overpower protection range 0…1100 W 0…1100 W 0…1100 W
Temperature coefcient for set values Δ/K Voltage / current: 100 ppm
Output capacitance (standard version)
~5440 μF ~5440 μF ~800 μF
Output capacitance (high speed version)
~86 μF ~86 μF ~40 μF
Voltage regulation
Adjustment range 0...40 V 0...80 V 0...200 V
Accuracy
(1
(at 23 ± 5 °C) < 0.1% U
Nom
< 0.1% U
Nom
< 0.1% U
Nom
Line regulation at ±10% ΔU
AC
< 0.02% U
Nom
< 0.02% U
Nom
< 0.02% U
Nom
Load regulation at 0...100% load < 0.05% U
Nom
< 0.05% U
Nom
< 0.05% U
Nom
Rise time 10...90% ΔU Max. 30 ms Max. 30 ms Max. 30 ms
Display: Resolution See section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.2% U
Nom
≤ 0.2% U
Nom
≤ 0.2% U
Nom
Ripple
(2
< 114 mV
PP
< 8 mV
RMS
< 114 mV
PP
< 8 mV
RMS
< 164 mV
PP
< 34 mV
RMS
Remote sensing compensation Max. 5% U
Nom
Max. 5% U
Nom
Max. 5% U
Nom
Output voltage fall time (at no load)after
switching DC output off
- -
Down from 100% to
<60 V: less than 10 s
Current regulation
Adjustment range 0...40 A 0...40 A 0...15 A
Accuracy
(1
(at 23 ± 5 °C) < 0.2% I
Nom
< 0.2% I
Nom
< 0.2% I
Nom
Line regulation at ±10% ΔU
AC
< 0.05% I
Nom
< 0.05% I
Nom
< 0.05% I
Nom
Load regulation at 0...100% ΔU
OUT
< 0.15% I
Nom
< 0.15% I
Nom
< 0.15% I
Nom
Ripple
(2
< 3.7 mA
RMS
< 3.7 mA
RMS
< 2.2 mA
RMS
Display: Resolution See section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.2% I
Nom
≤ 0.2% I
Nom
≤ 0.2% I
Nom
Transient time after load step < 1.5 ms < 1.5 ms < 1.5 ms
Power regulation
Adjustment range 0…1000 W 0…1000 W 0…1000 W
Accuracy
(1
(at 23 ± 5 °C) < 1% P
Nom
< 1% P
Nom
< 1% P
Nom
Line regulation at ±10% ΔU
AC
< 0.05% P
Nom
< 0.05% P
Nom
< 0.05% P
Nom
Load regulation at 10-90% ΔU
OUT
* ΔI
OUT
< 0.75% P
Nom
< 0.75% P
Nom
< 0.75% P
Nom
Display: Resolution See section „1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.8% P
Nom
≤ 0.8% P
Nom
≤ 0.8% P
Nom
Efciency
(3
~ 92% ~ 92% ~ 93%
(1 Related to the nominal values, the accuracy denes the maximum deviation between an adjusted values and the true (actual) value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20 MHz
(3 Typical value at 100% output voltage and 100% power
(4 The display error adds to the error of the related actual value on the DC output.