3BUS 208 000 R1301176 Maintenance Procedures
Inspecting the Incoming Power
Verify the presence of incoming power at the idler end column. The power for the
Scanning Platform comes through a transformer. The voltage to the transformer
must be of a nominal level (200, 208, 220, 230, or 240 volts) to connect to one of
the taps on the primary. The long-term variations from the nominal voltage must
not exceed
±10%.
Example: A 220 volt primary voltage must not average less than 198 VAC
or greater than 242 VAC for longer than one second.