3BUS 208 000 R1301138 Measurement Setup
Smart Basis Weight Sensors
Internal check sample may be automatically initiated at a dirty standardize. It will
be forced at each clean standardize. The variable NAUTO, available through the
inspect utility or the Basis Weight Health Report (see Figure 6-13), determines the
frequency of internal check sample relative to dirty standardize. If set to zero, there
will be no automatic internal check sample. If set to an integer (n) greater than 0,
then an automatic internal check sample will be run every n dirty standardize(s).
See Table 6-22 for the acceptable range of standardize limits for the Basis Weight
sensors.
Figure 6-13 NT Workstation BW Health Report - Standardize Limits