3BUS 208 000 R1301136 Measurement Setup
Health Report Standardize Reports
There are two standardize reports available on the Health Report: Pending (STDZ
Pend) and Current (STDZ Curr). The STDZ Pend report is the last standardize
results, either passed or failed, that was executed. The STDZ Curr report is the last
passed standardize and is the one the sensor would be currently using while scanning
or in single point. If the pending report shows failure, the sensor will still be able
to show a measurement on the Health Report; however, data sent to the host will be
marked invalid.
Changing the Standardize Mode of the FCP Standardize
Request
The default standardize mode requested from the FCP is DIRTY. This can be
changed to be CLEAN by changing and saving the mode flag in the FCP data base.
A reset is NOT needed to make the mode flag change active. Note that regardless
of the setting of the mode flag, a CLEAN standardize will always be performed
after a reset.
To change the mode flag, proceed as follows:
1. Activate the inspect utility.
2. Change the mode flag by typing:
I> fhi01->localStdzMode=x
where x =0 for DIRTY
1 for CLEAN
3. Exit the inspect utility by typing: :q
4. Save the change to the frame community using the gstore utility.