Specifications
PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
or other means of dissemination may be made without written permission.
3BUS 208 000 R1301 123Measurement Setup
Figure 6-5 NT Workstation Basis Weight Health Report - Calibration
Table 6-16 Basis Weight Sensor ATC Calibration Constants
Enter the calibration head constants into the Scanning Platform software through
the Basis Weight Health Report.
Basis Weight Sensor Model
ATC Constant TLK-5 TLK-8 TLK-9 TLP-1
KT0 0.0 0.09765 0.1758 0.0
KT1 0.5859 0.09375 0.2148 0.1953
KT2 -0.3477 0.2813 0.0 0.1953
KT3 0.0 0.0 0.0 0.0
dBWdT -0.1 -0.1 -0.1 -0.1