Using the Optional Temperature Controller Utility
1. At the $$ prompt, Type:
uc_heat n
(where n = 1 for BW head heaters)
6 for Ash head heaters
34 for IR head heaters
35 for Caliper probe
36 for HAW/CAP
39 for BW HAW/CAP heaters
2. When enter menu comes up, select 2 to change heater setup data.
3. When asked, select the desired controller number. The utility requests inputs
in the following order (xxx indicates the current value):
Enter temperature target scaled by 10 (or <cr> for xxx):
Are further changes needed for this heater controller? (y or n):
(answer n if just want to set target)
Thermister type 0 for 5k, 1 for 100k (<cr> for xxx):
Startup delay in seconds (<cr> for xxx):
Controller gain (K) scaled by 1000 (<cr> for xxx):
Integration constant (Bi) scaled by 1000 (<cr> for xxx):
Derivative constant (Nd) scaled by 1000 (<cr> for xxx):
Noise filter constant (alpha) scaled by 1000 (<cr> for xxx):
4. At the conclusion, the utility will respond with the line:
Enter heater controller number (0 - 3), 4 to send, or 5 to abort:
Either select a new controller on that same ECS board, send the new data to the
ECS board, or abort the process.
If all the microcontroller within the ECS board have been changed during the
session, the data will automatically be sent down without requesting it manually.
Current Microcontroller number is 0x1
Enter 1 to display heater data
2 to change heater setup data
3 to monitor one controller
4 to change microcontroller number
5 to quit this utility: 1