User guide
CLASS 5000 METER
62-0392-03 30
6.9.4 Dip Switch Settings
NOTE: *Protocol selections are done via DIP Switch (S2); pos 1 for RS-485 and pos
2 for Ethernet. When the DIP switch is in the ON position, EZ7 protocol will be
active. Changing protocol setting requires restarting the CPU. DIP Switch
indicating by X means don’t care.
NOTE: Pass Through Feature - S2 position 8 - to off - ethernet to RS485 pass
through - only valid with EZ7 protocol. -S2 position 8 - on - true dual protocol
settings.
Option
COMMUNICATION
PROTOCOLS
Firmware
PN#
PROTOCOL BAUD RATE
RS-485 Port
Ethernet
Port SW1 SW2 SW3 SW4
01 EZ7 EZ7 Modbus ON ON ON ON
02 Modbus RTU EZ7 Modbus OFF ON ON ON
03 BACnet MS/
TP
EZ7 BACnet
MS/TP
OFFONONOFF
04 EZ7 Modbus
TCP/IP
Modbus ON OFF ON ON
05 EZ7 BACnet IP BACnet IP ON OFF ON ON
06 Modbus RTU Modbus
TCP/IP
Modbus OFF OFF ON ON
07 LonWorks
TP/FT-10
EZ7 LonWorks X ON ON ON
08 LonWorks
TP/FT-10
Modbus
TCP/IP
LonWorks X OFF ON ON
09 EZ7 w/
Modem
EZ7 Modbus ON ON ON ON
10 EZ7 w/
Modem
Modbus
TCP/IP
Modbus ON OFF ON ON
11 EZ7 w/
Modem
BACnet IP BACnet IP ON OFF ON ON