Manual

GREEN CLASS METER
13 62-0415-01
4.4 MAINS Line Voltage & Current Sensor Wiring
Diagrams
Fig. 6. 3-Phase, 4-Wire Installation Diagram
Fig. 7. 3-Phase, 3-Wire Installation Diagram
A
B
LINE VOLTAGE
CURRENT SENSORS
A
N
B
LOAD SOURCE
M33185
3-PHASE, 4-WIRE INSTALLATION DIAGRAM
NOTES:
LINE VOLTAGE CONNECTIONS: #14-12 AWG
SENSOR CONNECTIONS: B = BLACK LEAD W = WHITE LEAD
NEUTRAL NOT USED IN DELTA SYSTEM. REMOVE NEUTRAL TERMINAL
BLOCK SCREW FOR DELTA SYSTEMS.
1/10A 600 VAC INLINE FUSE PER CONDUCTOR. LITTLEFUSE PART
NUMBER KLDR, 100.
1
1
1
C
1
C
A
B
C
W B W B
N
PE
W B
A
B
LINE VOLTAGE
CURRENT SENSORS
A
B
LOAD SOURCE
3-PHASE, 3-WIRE INSTALLATION DIAGRAM
NOTES:
LINE VOLTAGE CONNECTIONS: #14-12 AWG
SENSOR CONNECTIONS: B = BLACK LEAD W = WHITE LEAD
NEUTRAL NOT USED IN DELTA SYSTEM. REMOVE NEUTRAL TERMINAL
BLOCK SCREW FOR DELTA SYSTEMS.
1/10A 600 VAC INLINE FUSE PER CONDUCTOR. LITTLEFUSE PART
NUMBER KLDR, 100.
1
1
1
C
1
C
A
B
C
W B W B
N
PE
W B