Repeat the process for the B sensor gray plug. Connect only the B sensor plug to the B
phase current senor input terminal with the correct polarity (white to white and black to
black) the sensor error remains clears then the B sensor input leads polarity is correct
(see Fig. 11).
Fig. 11. Error LED
If the Error LED illuminates then reverse the input leads for B sensor by putting the
white leads on the black input and the black leads on the white input, (swapped
polarity). If it clears, the Error LED then tag as the B phase plug and take the gray plug
off the input marking them as B and note polarity to identify them later.
POWER LED
PULSE LED
ERROR LED
M34957