Cut Sheet
CLASS 1000 METER
ENGINEERING SPECIFICATIONS
Energy Monitoring Products & Systems
®
Energy Monitoring Products
®
Effective Date: 12/1/2012
(800) 334-3666 - www.emon.com
Meter shall be fully electronic with 2-line alpha-numeric LCD display for kilowatt-hour readings. Meter shall provide
rate of consumption indication and also a test sequence to ensure integrity of the display.
Meter shall provide a load indicator to indicate real-time consumption levels for field testing and certification.
Meter shall provide current sensor installation diagnostics indicator.
Meter shall use 0-2 volt output current sensors to allow paralleling and/or mounting up to 2,000 feet from the
meter. Sensors shall be of split-core configuration to allow installation without powering down. Sensors shall be
available from 25 amp to 200 amp. Sensors shall be optionally available in solid-core configuration (100 & 200 amp.)
Meter shall be enclosed in a heavy-duty JIC steel enclosure suitable for indoor installation. Meter enclosure
provides a method of locking to prevent unauthorized access.
Meter shall be optionally available in an outdoor NEMA 4X polycarbonate enclosure with padlocking hasp & mounting
flanges for indoor installation.
Meter shall be optionally available in MMU (Multiple Meter Configuration) enclosures containing up to 24 meters
in one compact enclosure.
Meter shall be UL Listed/CUL Listed to latest applicable standards for safety.
Meter shall be certified by a nationally recognized independent test facility to ANSI C12.20 (+/- 0.2% from 1% to 100%
of rated load) specifications.
Meter shall be California CTEP approved for use with solid-core current sensors, listed by the California Energy
Commission, New York City approved and Con Edison approved for RSP program.
Meter shall be provided with a non-volatile memory to maintain reading during power outages.
Meter shall be provided with modular connector(s) to provide interfacing with:
- AMR (Automatic Meter Reading)
- Building Management/Energy Management Systems
Meters shall be compatible with E-Mon Energy™ software.