User guide

CLASS 1000 METER
15 62-0388-01
Fig. 7. Single-Phase, 3-Wire Connection 120/240-Volt Single-Phase
A
B
C
A
B
W B W B N
LINE VOLTAGE
CURRENT SENSORS
A
N
SINGLE-PHASE, 3-WIRE CONNECTION
120/240-VOLT SINGLE-PHASE
B
LOAD SOURCE
M33180
NOTES:
LINE VOLTAGE CONNECTION: #14 AWG
SENSOR CONNECTION: B = BLACK W = WHITE
IMPORTANT: LINE VOLTAGE MUST BE PRESENT AT THE A- AND B-PHASE VOLTAGE TERMINALS.
SHORTING LINK MUST BE INSTALLED ON C-PHASE CURRENT SENSOR TERMINALS.
1/10-AMP INLINE FUSES RECOMMENDED.
1
1
1
PE