User Manual

Appendix: Technical Specifications 29
Terminals for wires size Blades (Socket meter standard –
C12.10)
Relay Output Digital output – combined SSR + EMR 4 x FORM C + 2 x FORM A
SSR – 4 relays (FORM C) 0.15A @ 250V AC/DC
Operation time
Release time
1 ms
1 ms
Insulation Dielectric withstand 2500V AC @ 1mn
EMR – 2 relays (FORM A), ½ cycle operation
5A @ 250V AC
Operation time
Release time
5-7 ms + ½ cycle
5-7 ms + ½ cycle
Insulation resistance of open contacts > 2 MΩ or 1000V @ 1mn
Insulation Dielectric withstand 2500V AC @ 1mn
6RO
Optional module
1
Terminals for wires size 16 x 2.5 mm
2
cable
Analog Outputs Analog output galvanic isolated 4
4-20 mA default
0-20 mA option
0-1 mA (2mA max.) option
Type of Outputs
± 1 mA (±2mA max.)option
Non-linearity 0.2%
Load for 20 mA <510 Ω
Accuracy 0.5%
Power supply Internal
Insulation Dielectric withstand 2500V AC @ 1mn
4AO
Optional module
1
Terminals for wires size 5 x 2.5 mm
2
cable
1
Factory/Meter shop installable