User Manual

Chapter 3 Communication 9
W iri n g C onf i g u rat io n Wiring Setup
FORM factor
4-wire WYE 3-element using 3 CTs 4Ln3 9S
4-wire WYE 3-element connection using 3 PTs, 3 CTs 4Ln3 9S
4-wire 3-element delta using 3 CTs 4LL3 9S
4-wire 3-element delta connection using 3 PTs, 3 CTs 4LL3 9S
3-wire 2½-element Open Delta connection using 3 CTs 3OP3 5S/35S
3-wire 2½-element Open Delta connection using 2 PTs, 3
CTs
3OP3 5S/35S
3-wire 2-element Open Delta using 2 CTs 3OP2
4-wire WYE 2½-element connection using 3 CTs 3Ln3 6S/36S
4-wire WYE 2½-element connection using 2 PTs, 3 CTs 3Ln3 6S/36S
4-wire 2½-element delta connection using 2 PTs, 3 CTs 3LL3
Tab le 1 : Wiri n g C o n f i gurat i o n
NOTE
In 4LN3 and 3LN3 wiring modes, the voltage readings for volt demands represent line-to-neutral
voltages; otherwise, they will be line-to-line voltages. The voltage waveforms and harmonics in
4LN3 and 3LN3 wiring modes represent line-to-neutral voltages; otherwise, they will be line-to-line
voltages
Figur e 8: Fo ur W i re WYE Co nn ec tion N o P Ts Usin g 3C Ts - W i r i n g Set u p :
4L n 3