Chapter 5 Configuring the PowerSmart Socket PQM
General Meter Setup
96 PowerSmart Socket Power Quality Meter
• ±2 mA: set the 1 mA scale to ½ of the required full-scale
output for both uni-directional and bi-directional parameters.
For example, to provide the 0 to 2 mA output current range
for Volts measured by the meter in the range of 0 to 120V,
set the 1 mA scale to 60V; then the 120V reading will be
scaled to 2 mA.