Instruction Manual
Chapter 5 Configuring the PowerSmart+ PQM Configuring Communications
74 PowerSmart+ Power Quality Meter
The following table lists available client options.
Table 7: TCP Notification Client Setup Options
Parameter Options Default Description
Client Enabled NO, YES NO Enables operations of the
notification client
Server IP Address 192.168.0.3 The IP address of the notification
server
Server Port 0-65535 502 The TCP service port of the
notification server
Message Exchange
Address
0-65535 1000 The start address of a block
of 16 MODBUS registers for
receiving notification messages
Connections with a remote server are triggered via programmable
setpoints. To send event notifications to a server, configure a setpoint to
respond to desired triggers or to periodic time events and put the
"Notification" action to the setpoint action list (see Configuring
Alarm/Control Setpoints).
See the PowerSmart+ PQM Modbus Reference guide for more information
on operation of the notification client and the notification message
structure.