Instruction Manual
Chapter 5 Configuring the PowerSmart+ PQM Configuring Communications
PowerSmart+ Power Quality Meter 73
The following table lists available options. Refer to your eXpertPower
service provider for the correct network settings.
Table 6: eXpertPower Client Setup Options
Parameter Options Default Description
XPW Server IP Address 207.232.60.18 The IP address of the
eXpertPower server
XPW Server Port 0-65535 5001 The TCP service port of the
eXpertPower server
XPW Client Enabled NO, YES NO Enables operations of the
eXpertPower client
Time to Next Session,
min
1-99999
The time remaining to the
next connection session
NOTES
6. Do not enable the eXpertPower client in your meter if you do not use
the eXpertPower
TM
service.
7. Do not change the connection time setting. It is for information only.
The eXpertPower server updates it automatically.
Setting Up TCP Notification Client
The TCP notification client can establish connections with a remote
MODBUS/TCP server and send notification messages either on events, or
periodically on a time basis.
To set up communications with a remote TCP Notification server, select
Communication Setup from the Meter Setup menu, and then click on
the TCP Notification Client Setup tab.
Figure 5-5: TCP Notification Client Setup Tab