Instruction Manual

Chapter 1 General Information Available Options
14 PowerSmart+ Power Quality Meter
Communications
Standard 2-wire RS-485 communication port; MODBUS RTU,
DNP3 communication protocols
Optional second communication port (see Available Options);
MODBUS RTU, MODBUS/TCP, DNP3, DNP3/TCP communication
protocols
eXpertPower client (see Setting Up eXpertPower Client)
TCP notification client for communicating with a remote
MODBUS/TCP server on events or periodically on a time basis
(with the Ethernet module or with the RS-232 module using an
external GPRS modem, see Setting Up TCP Notification Client)
Meter Security
Password security for protecting meter setups and accumulated
data from unauthorized changes
Upgradeable Firmware
Easy upgrading device firmware through a serial or Ethernet port.
Software Support
Power Software free meter configuration and data acquisition
tool
eXpertPower
TM
– Cloud AMR software services
1.2 Available Options
The PowerSmart+ PQM can be provided with an optional expansion
module from the following list:
Digital I/O
Analog outputs
TOU - Battery-operated clock unit
Ethernet communication port
PROFIBUS DP communication port
RS-232/RS-422/RS-485 communication port
GPRS communication port
Digital I/O
The PowerSmart+ PQM digital I/O expansion module provides:
4DI/2DO module
4 dry contact digital inputs (DI) for monitoring external contacts
and receiving pulses from energy, water, and gas meters
Programmable de-bounce time; 1-ms scan time.
2 electro-mechanical or solid-state relay outputs (RO) for alarms
and controls, and for output energy pulses; unlatched, latched
and pulse operations, failsafe operation for alarm notifications;
programmable pulse width; direct remote relay control through
communications; 1-cycle update time.
12DI/4DO module
12 dry contact digital inputs (DI) for monitoring external contacts
and receiving pulses from energy, water, and gas meters