Instruction Manual

Chapter 1 General Information Features
PowerSmart+ Power Quality Meter 13
Three-phase total and per phase energy measurements; active,
reactive and apparent energy counters
Time-of-Use, 4 totalization and tariff energy/demand registers x 8
tariffs, 4 seasons x 4 types of days, 8 tariff changes per day,
One–time easy programmable tariff calendar schedule
Automatic daily energy and maximum demand profile log for total
and tariff registers
Harmonic Analyzer
Voltage and current THD, current TDD and K-Factor, up to 40th
order harmonic
Voltage and current harmonic spectrum and angles
Real-time Waveform Capture
Real-time “scope mode” waveform monitoring capability
Simultaneous 6-channel one-cycle waveform capture at a rate of
64 samples per cycle
Programmable Logical Controller
Embedded programmable controller
16 control setpoints; programmable thresholds and delays
Relay output control (see Available Options)
1-cycle response time
Event and Data Recording
Non-volatile memory for long-term event and data recording
Event recorder for logging internal diagnostic events and setup
changes
Two data recorders; programmable data logs on a periodic basis;
automatic daily energy and maximum demand profile log
Digital I/O
Optional four digital inputs with 1-ms scan time; automatic
recording of last five digital input change events with timestamps
(see the PowerSmart+ PQM Modbus Reference Guide)
Optional two relay outputs with 1-cycle update time; unlatched,
latched, pulse and KYZ operation; energy pulses
Display
3.5 inch Monochrome Graphic LCD display with 240 x 128 dots
resolution, adjustable update time backlit and user defined
brightness setting
Auto-scroll option with adjustable page exposition time; auto-
return to a default page
LED bar graph showing percent load with respect to user-
definable nominal load current
Real-time Clock
Internal clock with 20-second retention time
Optional battery-operated clock unit (see Available Options)