Instruction Manual

Chapter 5 Configuring the PowerSmart+ PQM Configuring Communication Protocols
PowerSmart+ Power Quality Meter 105
The 32-bit Modbus registers are factory-set to integer format. To change
the register format:
1. Select Protocol Setup from the Meter Setup menu, and click on
the Modbus Registers tab.
2. Change the 32-bit register format in the Modbus Options pane.
3. Click Send to download your setup to the meter.
Configuring DNP3
Refer to the PowerSmart+ PQM DNP3 Reference guide for information on
the DNP3 protocol implementation and a list of the available data points.
DNP Options
Select Protocol Setup from the Meter Setup menu and click on the
DNP Options tab.
Figure 5-22: Protocol Setup Dialog Box DNP Options Tab
The following table describes available options. Refer to the DNP3 Data
Object Library document available from the DNP User’s Group on the
DNP3 object types.
Table 19: DNP Options
Parameter Options Default Description
Binary Inputs (BI)
Binary Input Object Single-bit
With Status
Single-bit The default BI object variation for
requests with qualifier code 06 when no
specific variation is requested
Analog Inputs (AI)
Analog Input Object 32-bit
32-bit–Flag
16-bit
16-bit–Flag
16-bit-Flag The default AI object variation for
requests with qualifier code 06 when no
specific variation is requested