Appendix E EN50160 Statistics L O G
F I L E S
146 PowerSmart+ Advanced Power Quality Meter
Field No.
Designation Description
12 N14 40%/1s Number of polyphase incidents u<40%/t<1s
13 N11 90%/3s Number of polyphase incidents u<90%/t<3s
14 N12 85%/3s Number of polyphase incidents u<85%/t<3s
15 N13 70%/3s Number of polyphase incidents u<70%/t<3s
16 N14 40%/3s Number of polyphase incidents u<40%/t<3s
17 N11 90%/20s Number of polyphase incidents u<90%/t<20s
18 N12 85%/20s Number of polyphase incidents u<85%/t<20s
19 N13 70%/20s Number of polyphase incidents u<70%/t<20s
20 N14 40%/20s Number of polyphase incidents u<40%/t<20s
21 N11 90%/60s Number of polyphase incidents u<90%/t<60s
22 N12 85%/60s Number of polyphase incidents u<85%/t<60s
23 N13 70%/60s Number of polyphase incidents u<70%/t<60s
24 N14 40%/60s Number of polyphase incidents u<40%/t<60s
25 N11 90%/180s Number of polyphase incidents u<90%/t<180s
26 N12 85%/180s Number of polyphase incidents u<85%/t<180s
27 N13 70%/180s Number of polyphase incidents u<70%/t<180s
28 N14 40%/180s Number of polyphase incidents u<40%/t<180s
29 V1 N1 Total number of incidents on phase V1
30 V1 Min Minimum residual voltage on phase V1
31 V2 N1 Total number of incidents on phase V2
32 V2 Min Minimum residual voltage on phase V2
33 V3 N1 Total number of incidents on phase V3
34 V3 Min Minimum residual voltage on phase V3
Voltage Interruptions (indicative statistics)
1 N1 1s Number of polyphase incidents t<1s
2 N2 180s Number of polyphase incidents t<180s
3 N3 >180s Number of polyphase incidents t>180s
4 V1 Min Minimum residual voltage on phase V1
5 V2 Min Minimum residual voltage on phase V2
6 V3 Min Minimum residual voltage on phase V3
Temporary Overvoltages (indicative statistics)
1 N11 110%/1s Number of polyphase incidents u>110%/t<1s
2 N12 120%/1s Number of polyphase incidents u>120%/t<1s
3 N13 140%/1s Number of polyphase incidents u>140%/t<1s
4 N14 160%/1s Number of polyphase incidents u>160%/t<1s
5 N15 200%/1s Number of polyphase incidents u>200%/t<1s
6 N21 110%/60s Number of polyphase incidents u>110%/t<60s
7 N22 120%/60s Number of polyphase incidents u>120%/t<60s
8 N23 140%/60s Number of polyphase incidents u>140%/t<60s
9 N24 160%/60s Number of polyphase incidents u>160%/t<60s
10 N25 200%/60s Number of polyphase incidents u>200%/t<60s
11 N31 110%/>60s Number of polyphase incidents u>110%/t>60s
12 N32 120%/>60s Number of polyphase incidents u>120%/t>60s
13 N33 140%/>60s Number of polyphase incidents u>140%/t>60s
14 N34 160%/>60s Number of polyphase incidents u>160%/t>60s
15 N35 200%/>60s Number of polyphase incidents u>200%/t>60s
16 V1 N1 Total number of incidents on phase V1
17 V1 Max Maximum voltage magnitude on phase V1
18 V2 N1 Total number of incidents on phase V2
19 V2 Max Maximum voltage magnitude on phase V2
20 V3 N1 Total number of incidents on phase V3
21 V3 Max Maximum voltage magnitude on phase V3
Transient Overvoltages (indicative statistics)
1 N1 110% Number of polyphase incidents u>120%
2 N2 150% Number of polyphase incidents u>150%
3 N3 200% Number of polyphase incidents u>200%
4 N4 250% Number of polyphase incidents u>250%
5 N5 300% Number of polyphase incidents u>300%
6 V1 N1 110% Number of incidents u>120% on phase V1
7 V1 N2 150% Number of incidents u>150% on phase V1
8 V1 N3 200% Number of incidents u>200% on phase V1
9 V1 N4 250% Number of incidents u>250% on phase V1
10 V1 N5 300% Number of incidents u>300% on phase V1
11 V2 N1 110% Number of incidents u>120% on phase V2
12 V2 N2 150% Number of incidents u>150% on phase V2