User Manual

Chapter 4 Power Software Configuration tool
Configuring Billing Energy and TOU Registers
50
Multi-Mon Multiple Circuit Energy Monitor
The available options are shown in the following table:
Parameter
ParameterParameter
Parameter
Options
OptionsOptions
Options
Default
DefaultDefault
Default
Description
DescriptionDescription
Description
Billing
BillingBilling
Billing/TOU Registers
/TOU Registers/TOU Registers
/TOU Registers
TOU Unchecked
Checked
Unchecked
Links tariff registers to the selected energy
source
Use Profl Unchecked
Checked
Unchecked
Enables automatic daily profiling for
energy usage registers (both total and
tariff registers if TOU is enabled)
Dmd Profl Unchecked
Checked
Unchecked
Enables automatic daily profiling for
maximum demand registers (both total
and tariff registers if TOU is enabled)
Sum Profl Unchecked
Checked
Unchecked
Enables daily profiling for summary
registers (total of all tariffs). Automatically
set when profiling is enabled.
Units kWh, kvarh, kVAh
None
The register measurement units. It is set
automatically.
Register Source List
Register Source ListRegister Source List
Register Source List
Source
Input
None
kWh IMPORT
kWh EXPORT
kvarh IMPORT
kvarh EXPORT
kVAh TOTAL
Submeter 1 -
Submeter 40
1
None
Links an energy source to the target
register of all metering submeters, or links
all registers of a source submeter to a
totalization submeter.
Multiplier 0.001 to 100.000 0.100
The multiplication factor for the energy
source.
Target Reg#1- Reg#3
Submeter 1 -
Submeter 40
1
None
Defines the target register for the energy
source. It is set automatically for target
energy registers.
1
Linking a submeter to another totalization submeter connects all its
configured energy registers to the corresponding registers of the target
submeter.