Owner's manual
DIN-MON™ SMART METER
69 62-0442—04
UCPTSendDeltaPhase_Angle 42 45 Min. time to propagate NV SNVT_count R/W
UCPTMinSndTReserve_A 43 45 Min. time to propagate NV SNVT_count R/W
UCPTMaxSndTReserve_A 43 45 Max. time to propagate NV SNVT_count R/W
UCPTSendDeltaReserve_A 43 45 Min. change in value to propagate SNVT_count_f R/W
UCPTMinSndTReserve_B 44 46 Min. time to propagate NV SNVT_count R/W
UCPTMaxSndTReserve_B 44 46 Max. time to propagate NV SNVT_count R/W
UCPTSendDeltaReserve_B 44 46 Min. change in value to propagate SNVT_count_f R/W
UCPTMinSndTReserve_C 45 47 Min. time to propagate NV SNVT_count R/W
UCPTMaxSndTReserve_C 45 47 Max. time to propagate NV SNVT_count R/W
UCPTSendDeltaReserve_C 45 47 Min. change in value to propagate SNVT_count_f R/W
UCPTMinSndTExt_Input_1 46 48 Min. time to propagate NV SNVT_count R/W
UCPTMaxSndTExt_Input_1 46 48 Max. time to propagate NV SNVT_count R/W
UCPTSendDeltaExt_Input_1 46 48 Min. change in value to propagate SNVT_count_f R/W
UCPTMinSndTExt_Input_2 47 49 Min. time to propagate NV SNVT_count R/W
UCPTMaxSndTExt_Input_2 47 49 Max. time to propagate NV SNVT_count R/W
UCPTSendDeltaExt_Input_2 47 49 Min. change in value to propagate SNVT_count_f R/W
UCPTMinSndTDateTime 49 52 Min. time to propagate NV SNVT_count R/W
* NOTE: BLK = Corresponding Function Block, VAR = Corresponding Network Variable,
SNVT = Standard Network Variable Type
NOTE DESCRIPTION
1 The MinSendTime configuration property corresponds to the shortest time that a bound
network variable needs to wait in order to propagate an update as long as the SendDelta
value has been exceeded.
2 The MaxSendTime configuration property corresponds to the longest time that a bound
network variable needs to wait in order to propagate an update regardless of the SendDelta
value.
3 The SendDelta configuration property corresponds to the difference in value between the
current and previous value that must be exceeded in order to propagate a bound network
variable.
The MinSendTime configuration property for the nvoRTC_DateTime network variable
corresponds to the frequency at which the date and time network variable is propagated.
CONFIG. PROPERTY BLK VAR DESCRIPTION UNITS R/W