Owner's manual
DIN-MON™ SMART METER
59 62-0442—04
41061 2 Float
Voltage, line phase B to N Volts-N R
41063
2
Float
Voltage, line phase C to N Volts-N R
41065 2 Float
Voltage, line phase A to B Volts-L R
41067
2
Float
Voltage, line phase B to C Volts-L R
41069 2 Float
Voltage, line phase C to A Volts-L R
41071
2
Float
Phase angle, phase A Degree R
41073
2
Float
Phase angle, phase B Degree R
41075 2 Float
Phase angle, phase C Degree R
44001
3
6
Custom
Interval Day Block R/W
44007
4
1*
Integer
Interval Data (1 register per
interval)
Pulse R
45501
5
2*
Custom
Interval Data Headers (2
registers per day)
R
46025
6
8
Custom
RTC Date/Time R/W
46049
7
8
Custom
EZ7 ID, Modbus ID, Serial R/W
46057
8
Custom
Recorder Info., Demand
Interval
R/W
46513
8
Custom
Flags L1: Power Failure,
Battery
R
46521
8
Custom
Flags L2: Power Failure Date R
1. To clear single meter kWh/kVARh, set multiple points at 40001 or 41001 for 8 points
with data set to 0000 0000 0000 0000 0000 0000 0000 0000. Jumper J6 must be closed.
2. N/A
3. To set the interval data day block, set multiple points at 44001 for 6 points with data set
to 0C0I 0000 MMDD YYYY 0000 0000. 0C = Channel, 0I = Interval (0F = 15 minute inter-
vals, 05 = 5 minute intervals).
4. Each register represents a 15 or 5 minute kWh pulse value based on the interval day
block. 96 registers max with 15 minute intervals. 288 registers max with 5 minute
intervals. The first interval data register 44007 represents the pulse count for the first
15 or 5 minute interval beginning at midnight.
5. The interval data headers represent days with available interval data. Each day repre-
sents 2 registers. Format: MMDD YYYY.
6. To set the date and time, set multiple points at 46025 for 4 points with data set to
HHMM SSDW MMDD YYYY (DW= day of week).
7. To change the ModBus ID, set single point at 46050 with data set to new ModBus
ID (e.g. 1 to 247). Jumper J6 must be closed.
ADDRESS REG TYPE DESCRIPTION UNITS R/W