Owner's manual

DIN-MON™ SMART METER
62-0442—04 58
APPENDIX A: MODBUS POINT MAP
ADDRESS REG TYPE DESCRIPTION UNITS R/W
40001
1
2 Integer
Energy delivered Wh Pulse R/W
40003
1
2
Integer
Energy received Wh Pulse R/W
40005
1
2 Integer
Reactive energy delivered VARh Pulse R/W
40007
1
2
Integer
Reactive energy received VARh Pulse R/W
41001
1
2
Float
Energy delivered kWh R/W
41003
1
2 Float
Energy received kWh R/W
41005
1
2
Float
Reactive energy delivered kVARh R/W
41007
1
2
Float
Reactive energy received kVARh R/W
41009
2
Float
Real power kW R
41011 2 Float
Reactive power kVAR R
41013
2
Float
Apparent power kVA R
41015
2
Float
Power factor % PF R
41017 2 Float
Peak demand kW R/W
41019 2 Float
Current average Amps R
41021
2
Float
Voltage line-neutral Volts-N R
41023 2 Float
Voltage line-line Volts-L R
41025
2
Float
Frequency Hz R
41027
2
Float
Phase angle Degree R
41029 2 Float
Real power, phase A kW R
41031
2
Float
Real power, phase B kW R
41033
2
Float
Real power, phase C kW R
41035
2
Float
Reactive power, phase A kVAR R
41037 2 Float
Reactive power, phase B kVAR R
41039
2
Float
Reactive power, phase C kVAR R
41041
2
Float
Apparent power, phase A kVA R
41043 2 Float
Apparent power, phase B kVA R
41045
2
Float
Apparent power, phase C kVA R
41047 2 Float
Power factor, phase A % PF R
41049
2
Float
Power factor, phase B % PF R
41051
2
Float
Power factor, phase C % PF R
41053 2 Float
Current, phase A Amps R
41055
2
Float
Current, phase B Amps R
41057
2
Float
Current, phase C Amps R
41059
2
Float
Voltage, line phase A to N Volts-N R